Electrical Component Parameter Reference

An open technical reference for electrical component types, their applications, and selection parameters.

This material is also available in PL and RU.

Device description

Neutral Distribution Block

Distribution block intended to connect and distribute neutral working conductors N among multiple electrical circuits.

A neutral distribution block is used to connect and distribute the neutral working potential N.

The block may provide one or more incoming connection points and multiple outgoing connections for neutral conductors of individual circuits.

Principal parameters include the number of incoming and outgoing connections, maximum total current, permissible current of individual outgoing connections, conductor cross-section ranges, and clamping technologies.

Terminal-opening dimensions, conductor entry depth, tightening torque, connection arrangement, and block mounting method are also important for installation.

A neutral distribution block forms part of the working electrical circuit and should be applied according to the earthing-system arrangement and method of neutral distribution.

Selection criteria include neutral current, number of outgoing circuits, conductor type, insulation requirements, and declared standards.

Components in this subcategory

This subcategory includes distribution blocks for connecting and distributing neutral conductors N.

Available parameters

Neutral Distribution Block

277 parameters
General6
Product Series

Commercial or technical designation of a manufacturer's product family sharing a common design and compatible characteristics.

Application

Range of tasks and systems for which the manufacturer recommends the component.

Intended Use

Primary function of the device and its intended use as defined by its design and the manufacturer's documentation.

Installation Location

Permissible installation location of the product: indoors, outdoors, in a technical area, or as part of equipment.

Installation Environment

Environmental conditions under which installation and operation of the product are permitted.

Orientation

Permissible spatial orientation of the component during installation and operation.

Dimensions11
Widthmm

External horizontal dimension of the product between its outermost lateral points.

Heightmm

External vertical dimension of the product from its lowest to its highest point.

Depthmm

External distance between the foremost and rearmost surfaces of the product.

Incoming Terminal Opening Widthmm

Clear width of the opening used to insert a conductor into the incoming terminal.

Incoming Terminal Opening Heightmm

Clear height of the opening used to insert a conductor into the incoming terminal.

Incoming Terminal Opening Diametermm

Clear diameter of the round opening used to insert a conductor into the incoming terminal.

Incoming Terminal Entry Depthmm

Mechanical conductor insertion depth from the entry surface of the incoming terminal to the design-defined stop or support point.

Outgoing Terminal Opening Widthmm

Clear width of the opening used to insert a conductor into the outgoing terminal.

Outgoing Terminal Opening Heightmm

Clear height of the opening used to insert a conductor into the outgoing terminal.

Outgoing Terminal Opening Diametermm

Clear diameter of the round opening used to insert a conductor into the outgoing terminal.

Outgoing Terminal Entry Depthmm

Mechanical conductor insertion depth from the surface of the outgoing terminal to the design-defined stop or support point.

Capacity and Layout23
Pole Configuration

Actual electrical pole configuration of the product, including the number and function of switched poles.

Connection Point Count

Total number of electrical connection points provided by the product.

Connection Pitchmm

Centre-to-centre pitch between adjacent repeated electrical connection points or contacts.

Incoming Connection Point Count

Number of electrical connection points intended for incoming or supply-side connections.

Outgoing Connection Point Count

Number of electrical connection points intended for outgoing or load-side connections.

Number of Electrical Potentials

Number of electrically independent potentials provided by the product design.

Connection Level Count

Number of vertically stacked or functionally distinct electrical connection levels.

Connections per Level

Number of electrical connection points provided on one connection level.

Maximum Incoming Conductors per Connection Point

Maximum number of conductors that may be connected simultaneously to one incoming connection point.

Maximum Outgoing Conductors per Connection Point

Maximum number of conductors that may be connected simultaneously to one outgoing connection point.

Incoming Connection Orientation

Physical direction from which a conductor enters an incoming or supply connection point.

Outgoing Connection Orientation

Physical direction from which a conductor enters an outgoing or load-side connection point.

Incoming Connection Pitchmm

Centre-to-centre distance between adjacent repeated incoming connection points.

Outgoing Connection Pitchmm

Centre-to-centre distance between adjacent repeated outgoing connection points.

Pole Pitchmm

Centre-to-centre distance between adjacent electrical poles or potential paths of a multipole product.

Incoming Connection Row Count

Number of physical rows containing incoming or supply connection points.

Outgoing Connection Row Count

Number of physical rows containing outgoing or load-side connection points.

Incoming Connections per Row

Number of incoming connection points arranged in one row.

Outgoing Connections per Row

Number of outgoing connection points arranged in one row.

Incoming Connection Row Pitchmm

Centre-to-centre distance between adjacent rows of incoming connection points.

Outgoing Connection Row Pitchmm

Centre-to-centre distance between adjacent rows of outgoing connection points.

Incoming Terminal Opening Shape

Geometric shape of the opening used to insert a conductor into the incoming terminal.

Outgoing Terminal Opening Shape

Geometric shape of the opening used to insert a conductor into the outgoing terminal.

Materials and Finish14
Color

Primary visually perceived colour of the product's external surface.

RAL Color

Designation of the product's primary surface colour according to the RAL colour system.

Electrically Insulating Material

Indicates whether the product's primary material has electrical insulating properties and is intended to electrically separate conductive parts.

Insulation Material

Primary electrical insulation material applied to or integrated with the conductive part of the product.

Insulation Thermal Class

Manufacturer-declared thermal class of the electrical insulation system or insulation material.

Insulating Material Group

Insulating material group used when evaluating creepage distances and insulation coordination.

Comparative Tracking IndexV

Comparative Tracking Index (CTI) of the insulating material, characterizing its resistance to formation of conductive tracks under specified test conditions.

Insulation Material Temperature Index°C

Manufacturer-declared temperature index of the insulating material.

Relative Temperature Index°C

Manufacturer-declared Relative Temperature Index (RTI) of the insulating material.

Current-Carrying Part Material

Primary material of the internal current-carrying part, bridge, busbar, or other conductive element of the product.

Current-Carrying Part Material Grade

Grade, alloy designation, or other declared material designation of the main current-carrying part.

Current-Carrying Part Plating

Metallic plating of the principal current-carrying part, different from its base material.

Clamping Element Material

Material of the mechanical clamping element, such as a screw, spring, pressure plate, or clamping cage.

Clamping Element Plating

Protective or functional metallic plating of the mechanical clamping element.

Mounting and Installation16
Fastener Material

Primary material of screws, bolts, nuts, rivets, and other product fasteners.

Mounting Type

Installation arrangement permitted by the product design, such as wall-mounted, flush-mounted, floor-mounted, or another specified mounting type.

Mounting Method

Method used to mechanically secure the product to a support, surface, or load-bearing structure.

Mounting Surface

Type of surface or supporting base to which the product may be fixed.

Number of Mounting Holes

Number of holes provided in the product for mechanical fixing.

Mounting Hole Diametermm

Diameter of the hole provided for a fixing element used when mounting the product.

Horizontal Mounting Hole Spacingmm

Distance between the centres of mounting holes in the horizontal direction.

Vertical Mounting Hole Spacingmm

Distance between the centres of mounting holes in the vertical direction.

Mounting Pattern Widthmm

Horizontal dimension of the mounting pattern between the outermost fixing points of the product.

Mounting Pattern Heightmm

Vertical dimension of the mounting pattern between the outermost fixing points of the product.

Mounting Screw Size

Size designation of the screw, bolt, or other threaded fastener used for mounting the product.

Mounting Thread

Designation of the thread provided in the product's mounting holes or fixing elements.

Mounting Tightening TorqueNm

Tightening torque recommended or permitted for fasteners during product installation.

Fasteners Included

Indicates whether the required fasteners are included with the product.

Direct Device Mounting Supported

Indicates whether equipment may be mounted directly to the mounting surface without an intermediate DIN rail.

Tool-Free Mounting

Indicates whether the intended installation of the product can be carried out without tools.

Electrical Parameters108
Supply Current Type

Type of electrical current for which the product's main supply circuit is intended.

Rated VoltageV

Voltage value assigned to the product by the manufacturer for specified application conditions and characteristics.

Rated AC VoltageV

Rated RMS value of alternating voltage assigned to the product by the manufacturer.

Rated DC VoltageV

Rated direct voltage assigned to the product by the manufacturer.

Rated Operational VoltageV

Operating-circuit voltage with reference to which the product's performance characteristics are specified.

Maximum Operating VoltageV

Maximum voltage at which continuous operation of the product is permitted under the conditions declared by the manufacturer.

Minimum Operating VoltageV

Minimum voltage at which the manufacturer guarantees the intended operating mode of the product.

Rated CurrentA

Current assigned to the product by the manufacturer for the declared operating and thermal conditions.

Maximum Rated CurrentA

Highest rated current permitted for the relevant version or configuration of the product.

Neutral Current Capacity Ratio%

Ratio of the permissible current-carrying capacity of the neutral conductor or busbar to the corresponding phase current capacity.

Maximum Incoming Conductor Cross-Sectionmm²

Maximum nominal conductor cross-section permitted at the product's incoming connection.

Maximum Outgoing Conductor Cross-Sectionmm²

Maximum nominal conductor cross-section permitted at the product's outgoing connection.

Maximum Neutral Conductor Cross-Sectionmm²

Maximum nominal cross-section of the neutral conductor permitted by the relevant product connection.

Supported Conductor Material

Conductor materials for which the specified terminals and connection methods are designed.

Conductor Connection Type

Conductor connection methods supported by the specified terminals or connection elements.

Terminal Tightening TorqueNm

Tightening torque specified by the manufacturer for a screw or bolted terminal connection.

Rated Insulation VoltageV

Voltage with reference to which the product's insulation clearances and dielectric properties are specified.

Rated Impulse Withstand VoltagekV

Peak value of an impulse voltage of specified waveform that the product insulation must withstand without breakdown.

Dielectric Test VoltageV

Test voltage applied to verify the dielectric strength of the product insulation.

Minimum Insulation ResistanceMΩ

Minimum permissible insulation resistance between the specified electrically separated parts.

Overvoltage Category

Category characterizing the expected level of impulse overvoltages at the product's point of use.

Pollution Degree

Degree of pollution of the surrounding microenvironment considered when selecting insulation distances and product characteristics.

Insulation Type

Type of electrical insulation used, considered in terms of its protective function and construction.

Electrical Protection Class

Class of protection against electric shock determined by the product design and protective connection method.

Rated Short-Time Withstand CurrentkA

RMS value of short-time withstand current Icw that the product can withstand for the declared duration without unacceptable damage.

Short-Time Withstand Durations

Duration for which the product must withstand the declared short-time current.

Rated Peak Withstand CurrentkA

Peak current value Ipk that the product can withstand under the declared short-circuit conditions.

Rated Conditional Short-Circuit CurrentkA

Prospective short-circuit current that the product can withstand when the specified external protective device is used.

Short-Circuit Current RatingkA

Manufacturer-declared permissible short-circuit current value for the product or assembly under specified conditions.

External Short-Circuit Protection Required

Indicates whether an external short-circuit protective device is required for the declared operation of the product.

Backup Protection Required

Indicates whether an additional upstream protective device is required to achieve the declared product characteristics.

Isolated Neutral Supported

Indicates whether the design permits the neutral busbar or conductor to be insulated from the enclosure.

Neutral Configuration

Arrangement of the neutral conductor or neutral busbar within the product.

Power Dissipation at Rated CurrentW

Thermal power loss of the product or current-carrying system at rated current.

Derating Factor

Factor used to reduce the permissible load relative to the rated value under specified conditions.

Reference Ambient Temperature°C

Ambient temperature to which the manufacturer's declared electrical or thermal characteristic applies.

Continuous Service CurrentA

Current that the product can carry continuously under the manufacturer's declared conditions without exceeding permissible temperature rise.

Minimum Incoming Conductor Cross-Sectionmm²

Minimum conductor cross-section permitted for connection to the incoming terminal of the main power circuit.

Minimum Outgoing Conductor Cross-Sectionmm²

Minimum conductor cross-section permitted for connection to the outgoing terminal of the main power circuit.

Minimum Neutral Conductor Cross-Sectionmm²

Minimum neutral conductor cross-section permitted for connection to the corresponding product terminal.

Supported Conductor Class

Conductor construction classes permitted by the product's electrical connection system.

Maximum Main Conductors per Terminal

Maximum number of main-power-circuit conductors that may be connected simultaneously to one terminal.

Maximum Backup Protection CurrentA

Maximum rated current of an external backup overcurrent protective device permitted by the manufacturer for use with the SPD.

Voltage Drop at Rated CurrentV

Manufacturer-declared voltage drop across the product, connection path or current-carrying element at rated current under the specified reference conditions.

Temperature Rise at Rated CurrentK

Manufacturer-declared temperature rise of the product above ambient temperature at rated current under the specified installation conditions.

Maximum Outgoing Connection CurrentA

Maximum manufacturer-declared continuous current permitted for an individual outgoing connection point. This is distinct from the total rated current of the product.

Incoming Connection Type

Electrical connection technologies supported at the incoming or supply-side connection points of the product.

Outgoing Connection Type

Electrical connection technologies supported at the outgoing or load-side connection points of the product.

Minimum Electrical Clearancemm

Minimum manufacturer-declared clearance through air between conductive parts at different electrical potentials.

Minimum Creepage Distancemm

Minimum manufacturer-declared creepage distance along an insulating surface between conductive parts at different electrical potentials.

Maximum Conductor Temperature°C

Maximum manufacturer-declared permissible temperature of the conductive part of the product in service.

Nominal Conductor Cross-Sectionmm²

Manufacturer-declared nominal conductor cross-section assigned to the relevant connection system.

Minimum Conductor Cross-Sectionmm²

Minimum conductor cross-section permitted by the connection system within its general conductor-size range.

Maximum Conductor Cross-Sectionmm²

Maximum conductor cross-section permitted by the connection system within its general conductor-size range.

Minimum Stripping Lengthmm

Minimum conductor stripping length specified by the manufacturer.

Maximum Stripping Lengthmm

Maximum conductor stripping length specified by the manufacturer.

Internal Cylindrical Gauge

Declared designation of the internal cylindrical gauge applicable to the conductor connection opening.

Maximum Total CurrentA

Maximum total current permitted by the manufacturer for the complete internally interconnected distribution product.

Maximum Incoming Connection CurrentA

Maximum continuous current permitted by the manufacturer for one incoming or supply connection point.

Incoming Nominal Conductor Cross-Sectionmm²

Declared nominal conductor cross-section assigned specifically to an incoming or supply connection.

Outgoing Nominal Conductor Cross-Sectionmm²

Declared nominal conductor cross-section assigned specifically to an outgoing or load-side connection.

Minimum Incoming Stripping Lengthmm

Minimum stripping length specified for an incoming or supply conductor.

Maximum Incoming Stripping Lengthmm

Maximum stripping length specified for an incoming or supply conductor.

Minimum Outgoing Stripping Lengthmm

Minimum stripping length specified for an outgoing or load-side conductor.

Maximum Outgoing Stripping Lengthmm

Maximum stripping length specified for an outgoing or load-side conductor.

Incoming Terminal Tightening TorqueNm

Manufacturer-declared tightening torque for an incoming or supply terminal.

Outgoing Terminal Tightening TorqueNm

Manufacturer-declared tightening torque for an outgoing or load-side terminal.

Supported Incoming Conductor Forms

Conductor forms and end-preparation methods permitted for the incoming connection.

Supported Outgoing Conductor Forms

Conductor forms and end-preparation methods permitted for the outgoing connection.

Minimum Incoming Rigid Conductor Cross-Sectionmm²

Minimum rigid conductor cross-section permitted for the incoming connection.

Maximum Incoming Rigid Conductor Cross-Sectionmm²

Maximum rigid conductor cross-section permitted for the incoming connection.

Minimum Incoming Flexible Conductor Cross-Sectionmm²

Minimum flexible conductor cross-section permitted for the incoming connection.

Maximum Incoming Flexible Conductor Cross-Sectionmm²

Maximum flexible conductor cross-section permitted for the incoming connection.

Minimum Incoming Ferrule Cross-Section without Sleevemm²

Minimum incoming flexible conductor cross-section when fitted with a ferrule without an insulating plastic collar.

Maximum Incoming Ferrule Cross-Section without Sleevemm²

Maximum incoming flexible conductor cross-section when fitted with a ferrule without an insulating plastic collar.

Minimum Incoming Ferrule Cross-Section with Sleevemm²

Minimum incoming flexible conductor cross-section when fitted with a ferrule with an insulating plastic collar.

Maximum Incoming Ferrule Cross-Section with Sleevemm²

Maximum incoming flexible conductor cross-section when fitted with a ferrule with an insulating plastic collar.

Minimum Incoming TWIN Ferrule Cross-Sectionmm²

Minimum cross-section of each of two incoming conductors permitted for joint connection using a TWIN ferrule.

Maximum Incoming TWIN Ferrule Cross-Sectionmm²

Maximum cross-section of each of two incoming conductors permitted for joint connection using a TWIN ferrule.

Minimum Direct-Pluggable Incoming Rigid Cross-Sectionmm²

Minimum rigid incoming conductor cross-section suitable for direct insertion into a compatible push-in connection.

Maximum Direct-Pluggable Incoming Rigid Cross-Sectionmm²

Maximum rigid incoming conductor cross-section suitable for direct insertion into a compatible push-in connection.

Minimum Direct-Pluggable Incoming Ferrule Cross-Section without Sleevemm²

Minimum incoming conductor cross-section with a ferrule without a plastic collar suitable for direct insertion.

Maximum Direct-Pluggable Incoming Ferrule Cross-Section without Sleevemm²

Maximum incoming conductor cross-section with a ferrule without a plastic collar suitable for direct insertion.

Minimum Direct-Pluggable Incoming Ferrule Cross-Section with Sleevemm²

Minimum incoming conductor cross-section with a ferrule with a plastic collar suitable for direct insertion.

Maximum Direct-Pluggable Incoming Ferrule Cross-Section with Sleevemm²

Maximum incoming conductor cross-section with a ferrule with a plastic collar suitable for direct insertion.

Minimum Outgoing Rigid Conductor Cross-Sectionmm²

Minimum rigid conductor cross-section permitted for the outgoing connection.

Maximum Outgoing Rigid Conductor Cross-Sectionmm²

Maximum rigid conductor cross-section permitted for the outgoing connection.

Minimum Outgoing Flexible Conductor Cross-Sectionmm²

Minimum flexible conductor cross-section permitted for the outgoing connection.

Maximum Outgoing Flexible Conductor Cross-Sectionmm²

Maximum flexible conductor cross-section permitted for the outgoing connection.

Minimum Outgoing Ferrule Cross-Section without Sleevemm²

Minimum outgoing flexible conductor cross-section when fitted with a ferrule without an insulating plastic collar.

Maximum Outgoing Ferrule Cross-Section without Sleevemm²

Maximum outgoing flexible conductor cross-section when fitted with a ferrule without an insulating plastic collar.

Minimum Outgoing Ferrule Cross-Section with Sleevemm²

Minimum outgoing flexible conductor cross-section when fitted with a ferrule with an insulating plastic collar.

Maximum Outgoing Ferrule Cross-Section with Sleevemm²

Maximum outgoing flexible conductor cross-section when fitted with a ferrule with an insulating plastic collar.

Minimum Outgoing TWIN Ferrule Cross-Sectionmm²

Minimum cross-section of each of two outgoing conductors permitted for joint connection using a TWIN ferrule.

Maximum Outgoing TWIN Ferrule Cross-Sectionmm²

Maximum cross-section of each of two outgoing conductors permitted for joint connection using a TWIN ferrule.

Minimum Direct-Pluggable Outgoing Rigid Cross-Sectionmm²

Minimum rigid outgoing conductor cross-section suitable for direct insertion into a compatible push-in connection.

Maximum Direct-Pluggable Outgoing Rigid Cross-Sectionmm²

Maximum rigid outgoing conductor cross-section suitable for direct insertion into a compatible push-in connection.

Minimum Direct-Pluggable Outgoing Ferrule Cross-Section without Sleevemm²

Minimum outgoing conductor cross-section with a ferrule without a plastic collar suitable for direct insertion.

Maximum Direct-Pluggable Outgoing Ferrule Cross-Section without Sleevemm²

Maximum outgoing conductor cross-section with a ferrule without a plastic collar suitable for direct insertion.

Minimum Direct-Pluggable Outgoing Ferrule Cross-Section with Sleevemm²

Minimum outgoing conductor cross-section with a ferrule with a plastic collar suitable for direct insertion.

Maximum Direct-Pluggable Outgoing Ferrule Cross-Section with Sleevemm²

Maximum outgoing conductor cross-section with a ferrule with a plastic collar suitable for direct insertion.

Connection Contact ResistancemΩ

Declared electrical contact resistance of a connection point where one common value applies to equivalent connections.

Incoming Connection Contact ResistancemΩ

Declared electrical contact resistance of an incoming or supply connection.

Outgoing Connection Contact ResistancemΩ

Declared electrical contact resistance of an outgoing or load-side connection.

Maximum Terminal Temperature RiseK

Maximum permissible temperature rise of a terminal or connection point under the declared test or operating conditions.

Short-Time Withstand Reference Conductor Cross-Sectionmm²

Cross-section of the connected conductor associated with the declared or tested short-time withstand current value.

Backup Protection Device Type

Type of upstream overcurrent protective device permitted or required by the manufacturer for the declared conditional short-circuit withstand rating or SCCR.

Short-Circuit Rating Conditions

Conditions associated with the declared short-circuit withstand rating or SCCR, including required type, class, rating, or other restrictions of the upstream protective device.

Protection and Safety12
Halogen-Free

Indicates whether the product material is classified as halogen-free according to the characteristics declared by the manufacturer.

IP Rating

Degree of enclosure protection against access to hazardous parts and ingress of solid objects and water, designated by the IP code.

Protection Against Direct Contact

Method or level of protection of the user against direct contact with hazardous live parts.

Finger-Safe

Indicates whether the design prevents finger access to hazardous live parts in the intended condition.

Touch-Safe

Indicates whether the design provides protection against accidental contact with hazardous live parts.

Protective Shrouds Included

Indicates whether insulating or mechanical protective shrouds are included with the product.

Live Parts Covered

Indicates whether live parts are covered by protective elements in the intended product state.

Flammability Class

Classification of a material according to its ability to ignite, sustain combustion, and cease burning under a specified test.

Glow-Wire Test Temperature°C

Temperature of the heated wire used when testing the material or product against an ignition source.

Self-Extinguishing

Indicates whether the material ceases self-sustained burning after the ignition source is removed under specified conditions.

Terminal Cover Supported

Indicates whether the product is compatible with insulating terminal covers or protective terminal shrouds.

Terminal Cover Included

Indicates whether insulating terminal covers or protective terminal shrouds are supplied with the product.

Environmental Conditions23
Minimum Operating Temperature°C

Minimum ambient temperature at which normal operation of the product is permitted.

Maximum Operating Temperature°C

Maximum ambient temperature at which normal operation of the product is permitted.

Maximum 24-Hour Average Temperature°C

Maximum permissible average ambient temperature over a consecutive 24-hour period.

Minimum Storage Temperature°C

Minimum ambient temperature permitted during storage of the product while not in operation.

Maximum Storage Temperature°C

Maximum ambient temperature permitted during storage of the product while not in operation.

Minimum Transport Temperature°C

Minimum ambient temperature permitted during transportation of the product.

Maximum Transport Temperature°C

Maximum ambient temperature permitted during transportation of the product.

Minimum Installation Temperature°C

Minimum ambient temperature at which the manufacturer permits installation of the product.

Maximum Installation Temperature°C

Maximum ambient temperature at which the manufacturer permits installation of the product.

Temperature Derating Required

Indicates whether permissible electrical or thermal loading must be reduced as temperature changes.

Temperature Derating Start°C

Temperature above which the permissible product load must be reduced.

Temperature Derating Curve Available

Indicates whether the manufacturer has published the relationship between permissible product load and temperature.

Minimum Relative Humidity%

Minimum relative air humidity permitted for the declared operating or test condition.

Maximum Relative Humidity%

Maximum relative air humidity permitted for the declared operating or test condition.

Relative Humidity Reference Temperature°C

Temperature at which the corresponding relative humidity value is specified or standardized.

Non-Condensing Humidity

Indicates whether the permissible humidity value applies only to non-condensing conditions.

Maximum Installation Altitudem

Maximum altitude above sea level at which the product may be installed without exceeding the declared conditions.

Altitude Derating Required

Indicates whether the permissible product load must be reduced as installation altitude increases.

Altitude Derating Startm

Altitude above sea level above which the permissible product load must be reduced.

Vibration Resistant

Indicates whether the product's resistance to vibration has been verified under the declared conditions.

Mechanical Shock Resistant

Indicates whether the product's resistance to short-duration mechanical shocks has been verified.

Environmental Test Standard

Standard or method used for climatic, mechanical, or combined testing of the product.

Minimum Cold Application Temperature of Insulating Material°C

Minimum declared temperature for static use of the insulating material under cold conditions, distinct from the minimum operating temperature of the complete product.

Included Equipment4
Installation Hardware Kit Included

Indicates whether an installation hardware kit is included in the product's standard equipment.

Documentation Included

Indicates whether documentation is included in the product's standard supply.

Installation Manual Included

Indicates whether an installation manual is included with the product.

End Cover Included

Indicates whether the required or applicable end cover is supplied with the product.

Special Features7
Internal Bridging Present

Indicates whether multiple connection points are electrically interconnected by an internal current-carrying bridge.

External Bridging Supported

Indicates whether external electrical bridging of connection points or adjacent products is supported.

External Bridging Method

Supported technologies or methods for providing an external electrical bridging connection.

Disconnect Function Present

Indicates whether the product design provides an intentional electrical disconnect function.

Test Point Present

Indicates whether the product includes an integrated electrical point for testing or measurement.

Open Side Panel

Indicates whether the product has an open side that may require an end cover, adjacent device, or another closing element.

End Cover Required

Indicates whether a separate end cover or closing plate is required to complete installation or the electrical insulation system.

Standards and Compliance43
Conformity Regions

Regions or markets for which the manufacturer declares regulatory or certification compliance of the product.

Certification and Conformity Marks

Certification, market-approval, or conformity marks applicable to the product.

Primary Product Standard

Primary normative document or standard according to which the manufacturer classifies or assesses the product.

Additional Standards

Additional normative documents and standards declared by the manufacturer as applicable to the product.

Declaration of Conformity Available

Indicates whether an official declaration of conformity is available for the product.

Manufacturer Declaration Available

Indicates whether a separate manufacturer declaration concerning declared product characteristics or conformity is available.

Certificate Available

Indicates whether a certificate relating to the declared certification or conformity of the product is available.

Certificate Number

Identification number of the certificate relating to the product or its certified version.

Certification Body

Name of the organization that issued the certificate or performed the relevant conformity assessment.

Third-Party Tested

Indicates whether the product was tested by an organization independent of the manufacturer.

Test Report Available

Indicates whether a test report confirming the declared product characteristics is available.

Type Test Report Available

Indicates whether a type-test report for the product or relevant design is available.

Routine Test Report Available

Indicates whether a report of routine or acceptance tests on the manufactured product is available.

Design Verification Available

Indicates whether documented confirmation of design verification for the product or assembly is available.

Verification Method

Methods used to verify that the design complies with the declared requirements.

CE Marked

Indicates whether the CE marking is applied to the product where applicable.

UKCA Marked

Indicates whether the UKCA marking is applied to the product where applicable.

EAC Marked

Indicates whether the EAC marking is applied to the product where applicable.

UL Listed

Indicates whether the product has a declared UL Listed certification or recognition status.

UL Recognized

Indicates whether the product has a declared UL Recognized certification or recognition status.

cULus Marked

Indicates whether the cULus mark is applied to the product where applicable.

CSA Certified

Indicates whether the product has a declared CSA certification or recognition status.

TÜV Certified

Indicates whether the product has a declared TÜV certification or recognition status.

VDE Certified

Indicates whether the product has a declared VDE certification or recognition status.

RoHS Compliant

Indicates whether product compliance with applicable RoHS restrictions on hazardous substances has been declared.

REACH Compliant

Indicates whether the manufacturer declares compliance of the product with applicable REACH Regulation requirements.

WEEE Applicable

Indicates whether the product falls within the scope of WEEE requirements for waste electrical and electronic equipment.

Suitable for Use as Service Equipment

Indicates manufacturer-declared suitability of the product for use as service equipment where that classification is applicable.

IEC 60947-7-1 Compliant

Indicates declared compliance with the applicable IEC 60947-7-1 requirements for terminal blocks for copper conductors and test disconnect terminal blocks where applicable.

IEC 60947-7-2 Compliant

Indicates declared compliance with the applicable IEC 60947-7-2 requirements for PE/PEN protective-conductor terminal blocks where applicable.

UL 1059 Compliant

Indicates declared compliance with the applicable UL 1059 requirements for terminal blocks, including protective-conductor terminal blocks where applicable.

IEC 60998-1 Compliant

Indicates declared compliance of the product with the applicable general requirements of IEC 60998-1 for connecting devices for low-voltage circuits for household and similar purposes.

IEC 60998-2-1 Compliant

Indicates declared compliance of the product with the applicable IEC 60998-2-1 requirements for separate connecting devices with screw-type clamping units.

IEC 60998-2-2 Compliant

Indicates declared compliance of the product with the applicable IEC 60998-2-2 requirements for separate connecting devices with screwless clamping units.

IEC 60999-1 Compliant

Indicates declared compliance of the product with the applicable IEC 60999-1 requirements for screw-type and screwless clamping units for the relevant copper conductor sizes.

IEC 60999-2 Compliant

Indicates declared compliance of the product with the applicable IEC 60999-2 requirements for clamping units for conductors of the relevant larger cross-sections.

UL 1953 Compliant

Indicates declared compliance of the product with the applicable UL 1953 requirements for power distribution blocks.

Suitable for Feeder Circuits

Indicates manufacturer-declared suitability of the product for use in feeder circuits where this classification is applicable.

Suitable for Branch Circuits

Indicates manufacturer-declared suitability of the product for use in branch circuits where this classification is applicable.

Suitable for Line Side of Service Equipment

Indicates manufacturer-declared suitability of the product for installation on the line side of service equipment where permitted by the applicable certification and installation rules.

Suitable for Load Side of Service Equipment

Indicates manufacturer-declared suitability of the product for installation on the load side of service equipment.

EN 50155 Compliant

Indicates declared compliance or qualification of the product with the applicable EN 50155 requirements for railway rolling-stock equipment.

IEC 61373 Compliant

Indicates declared compliance of the product with the applicable IEC 61373 shock and vibration requirements for railway rolling-stock equipment.

Logistics10
Net Weightkg

Mass of the product itself, excluding transport packaging, additional accessories, and external equipment.

Gross Weightkg

Mass of the product together with its individual packaging and the accessories included in it.

Package Widthmm

External horizontal dimension of the product's individual package.

Package Heightmm

External vertical dimension of the product's individual package.

Package Depthmm

External depth dimension of the product's individual package.

Packaging Type

Design type of the product's individual or transport packaging.

Units per Package

Number of individual products contained in one packaging unit at the specified level.

Country of Origin

Country of origin of the goods declared for customs or commercial purposes.

HS Code

Commodity code under the international Harmonized Commodity Description and Coding System.

Combined Nomenclature Code

Commodity code under the Combined Nomenclature of the European Union.