Device description

Overcurrent Relay

Monitoring relay intended to detect when the monitored current exceeds a configured upper threshold.

An overcurrent relay monitors circuit current and detects when the measured value exceeds the configured upper limit.

Measurement may be direct, through an external current transformer, or by another manufacturer-specified method. The threshold may be set as an absolute current value or relative to a nominal or reference current.

When the threshold is exceeded, the device changes its output state. Adjustable delay and hysteresis may be used to prevent unwanted operation. Selection criteria include measuring range, input overload capability, connection method, threshold range, accuracy, delay, and output characteristics.

Components in this subcategory

Overcurrent relays, upper-current-threshold monitoring devices, and multifunction monitoring relays whose primary function is detection of excessive current.

Available parameters

Overcurrent Relay

272 parameters
General7
Product Series

Commercial or technical designation of a manufacturer's product family sharing a common design and compatible characteristics.

Application

Range of tasks and systems for which the manufacturer recommends the component.

Intended Use

Primary function of the device and its intended use as defined by its design and the manufacturer's documentation.

Installation Location

Permissible installation location of the product: indoors, outdoors, in a technical area, or as part of equipment.

Installation Environment

Environmental conditions under which installation and operation of the product are permitted.

Orientation

Permissible spatial orientation of the component during installation and operation.

Monitoring Domains Supported

High-level electrical or process monitoring domains supported by the product.

Dimensions3
Widthmm

External horizontal dimension of the product between its outermost lateral points.

Heightmm

External vertical dimension of the product from its lowest to its highest point.

Depthmm

External distance between the foremost and rearmost surfaces of the product.

Capacity and Layout6
Relay Output Count

Number of independent relay outputs or sets of switching contacts provided by the product.

Relay Output Contact Configuration

Contact configurations provided for the product relay outputs.

Relay Output Functions

Functions permanently assigned or assignable to the product relay outputs.

Normally Open Relay Contact Count

Number of normally open switching contact sets provided by the relay.

Normally Closed Relay Contact Count

Number of normally closed switching contact sets provided by the relay.

Changeover Relay Contact Count

Number of changeover contact sets provided by the relay.

Materials and Finish5
Color

Primary visually perceived colour of the product's external surface.

RAL Color

Designation of the product's primary surface colour according to the RAL colour system.

Surface Finish

Type of final surface finish of the product determining its appearance and service properties.

Material

Primary material from which the product is manufactured.

Material Grade

Grade, alloy, class, or technical designation of the product's primary material.

Mounting and Installation5
DIN Rail Type

Profile type of the DIN rail installed in the product or specified for compatible mounting.

Mounting Type

Installation arrangement permitted by the product design, such as wall-mounted, flush-mounted, floor-mounted, or another specified mounting type.

Mounting Method

Method used to mechanically secure the product to a support, surface, or load-bearing structure.

DIN Rail Mounting Supported

Indicates whether the design provides for mounting equipment on a DIN rail.

Direct Device Mounting Supported

Indicates whether equipment may be mounted directly to the mounting surface without an intermediate DIN rail.

Electrical Parameters150
Rated Insulation VoltageV

Voltage with reference to which the product's insulation clearances and dielectric properties are specified.

Rated Impulse Withstand VoltagekV

Peak value of an impulse voltage of specified waveform that the product insulation must withstand without breakdown.

Dielectric Test VoltageV

Test voltage applied to verify the dielectric strength of the product insulation.

Minimum Insulation ResistanceMΩ

Minimum permissible insulation resistance between the specified electrically separated parts.

Overvoltage Category

Category characterizing the expected level of impulse overvoltages at the product's point of use.

Pollution Degree

Degree of pollution of the surrounding microenvironment considered when selecting insulation distances and product characteristics.

Insulation Type

Type of electrical insulation used, considered in terms of its protective function and construction.

Electrical Protection Class

Class of protection against electric shock determined by the product design and protective connection method.

Relay Contact Maximum Switching PowerW

Maximum manufacturer-declared active power that may be switched by the relay-output contacts.

Response Timens

Manufacturer-declared response time of the relevant protective function of the product to a surge impulse.

Maximum Measurement Cycle Timems

Maximum manufacturer-declared time required to complete one measurement and evaluation cycle of the monitoring function.

Monitoring Supply Mode

Relationship between the monitored measuring circuit and the electrical supply required for operation of the monitoring or indication function.

Monitoring Threshold Reference Mode

Defines whether a monitoring threshold is specified as an absolute measured value or relative to a nominal or measuring-range value.

Monitored Current Type

Current type of the monitored measuring circuit: AC, DC or AC/DC.

Current Evaluation Quantities

Types of current quantities evaluated by the monitoring device, for example RMS, active-current component or apparent current.

Nominal Monitored CurrentA

Nominal current used as the reference value for current monitoring and relative threshold settings.

Minimum Monitored CurrentA

Lower limit of the manufacturer-declared current measuring range.

Maximum Monitored CurrentA

Upper limit of the manufacturer-declared current measuring range.

Current Measurement Accuracy%

Manufacturer-declared relative accuracy of current measurement where expressed as a percentage.

Current Threshold Setting Accuracy%

Manufacturer-declared accuracy of the configured current monitoring threshold.

Current Monitoring Repeat Accuracy%

Repeat accuracy of current threshold detection under constant reference conditions.

Current Monitoring Temperature Coefficient%/K

Change of current monitoring accuracy per degree of temperature variation.

Monitored Current Input ResistanceΩ

Electrical resistance of the current measuring input.

Minimum Monitored Current FrequencyHz

Minimum AC current frequency supported by the measuring input.

Maximum Monitored Current FrequencyHz

Maximum AC current frequency supported by the measuring input.

Continuous Current Input LimitA

Maximum current that may be continuously applied to the measuring input without exceeding manufacturer-declared limits.

Maximum Current Input OverloadA

Maximum short-duration current that the measuring input can withstand.

Current Input Overload Durations

Duration associated with the declared short-duration current input overload capability.

Minimum Current HysteresisA

Minimum configurable current hysteresis expressed as an absolute current difference.

Maximum Current HysteresisA

Maximum configurable current hysteresis expressed as an absolute current difference.

Current Measurement Connection Method

Supported methods for connecting the monitored current to the measuring device.

Minimum Current Transformer Ratio

Minimum configurable primary-to-secondary current transformer ratio.

Maximum Current Transformer Ratio

Maximum configurable primary-to-secondary current transformer ratio.

Current Input BurdenVA

Apparent-power burden presented by the measuring input to an external current transformer under manufacturer-declared conditions.

Minimum Shunt Input VoltageV

Minimum supported measuring voltage across an external current shunt. UI may display the value in mV.

Maximum Shunt Input VoltageV

Maximum supported measuring voltage across an external current shunt. UI may display the value in mV.

Supply Current Type

Type of electrical current for which the product's main supply circuit is intended.

Rated VoltageV

Voltage value assigned to the product by the manufacturer for specified application conditions and characteristics.

Rated AC VoltageV

Rated RMS value of alternating voltage assigned to the product by the manufacturer.

Rated DC VoltageV

Rated direct voltage assigned to the product by the manufacturer.

Rated FrequencyHz

AC frequency assigned to the product for normal operating conditions.

Auxiliary Supply VoltageV

Rated external auxiliary supply voltage required for the product's active functions.

Auxiliary Supply Type

Type of current and source used for the product's auxiliary supply.

Maximum Power DissipationW

Maximum thermal power loss that the product can dissipate under specified conditions.

Power Dissipation at Rated CurrentW

Thermal power loss of the product or current-carrying system at rated current.

Supported Conductor Material

Conductor materials for which the specified terminals and connection methods are designed.

Conductor Connection Type

Conductor connection methods supported by the specified terminals or connection elements.

Terminal Tightening TorqueNm

Tightening torque specified by the manufacturer for a screw or bolted terminal connection.

Monitoring Functions

Electrical or physical monitoring functions provided by the device, such as overvalue, undervalue, window, phase, frequency, current, power, insulation, temperature or level monitoring.

Measurement Principle

Electrical measurement principle used for evaluation of the monitored signal, such as true RMS, RMS, average-value or direct-value measurement.

Measuring Input Type

Physical or electrical input technology used for acquisition of the monitored quantity, for example direct voltage, direct current, current transformer, resistance sensor, thermistor or conductive probe.

Measured Signal Current Type

Current type accepted by the measuring input, such as AC, DC or AC/DC.

Measuring Input Count

Number of independent physical measuring inputs provided by the device.

Galvanically Isolated Measuring Input

Indicates whether the measuring input is galvanically isolated from the supply, output or other relevant circuits.

Self-Powered from Measured Circuit

Indicates that the monitoring device derives its operating power directly from the measured circuit and does not require a separate auxiliary supply.

Minimum Measurement FrequencyHz

Minimum signal frequency accepted by the measuring circuit for the declared monitoring or measurement function.

Maximum Measurement FrequencyHz

Maximum signal frequency accepted by the measuring circuit for the declared monitoring or measurement function.

Measuring Input ResistanceΩ

Manufacturer-declared electrical resistance of the measuring input where applicable.

Measurement Accuracy%

Manufacturer-declared accuracy of the measured value under the specified reference conditions.

Threshold Setting Accuracy%

Manufacturer-declared accuracy or tolerance of the configured monitoring threshold.

Repeat Accuracy%

Manufacturer-declared repeatability of switching, alarm or monitoring operation under unchanged reference conditions.

Temperature Coefficient%/K

Manufacturer-declared change of measuring or switching accuracy per unit change of ambient temperature.

Monitoring Threshold Count

Number of independently usable monitoring, switching or alarm thresholds provided by the device.

Threshold Setting Methods

Methods available for setting monitoring thresholds, such as potentiometer, rotary selector, DIP switch, buttons, software or NFC configuration.

Adjustable Response Delay

Indicates that the intentional delay between detection of a monitored fault condition and output operation can be adjusted.

Minimum Response Delays

Minimum configurable response delay between fault detection and monitoring output operation.

Maximum Response Delays

Maximum configurable response delay between fault detection and monitoring output operation.

Fixed Response Delays

Fixed manufacturer-declared intentional response delay where the monitoring device does not provide an adjustable delay.

Recovery Times

Time required for the monitoring function or output to recover after the monitored quantity has returned to the permissible range.

Power Failure Buffering Times

Maximum supply interruption duration that can be tolerated without loss of the relevant operating or monitoring state.

Window Monitoring Supported

Indicates support for monitoring whether the measured value remains inside or outside a defined lower-to-upper threshold window.

Independent Upper and Lower Thresholds

Indicates that the upper and lower limits of a monitoring window can be configured independently.

Measurement Range Count

Number of discrete measurement ranges supported by the measuring input.

Selectable Measurement Range

Indicates that the measuring range can be selected or configured by the user.

Measurement Range Selection Method

Method used to select the active measuring range, such as automatic range selection, rotary control, DIP switch, wiring selection or software configuration.

Monitoring Output Operating Principle

Operating principle of the monitoring relay output with respect to normal and fault conditions, such as normally energized, normally de-energized or selectable behaviour.

Threshold Reference Mode

Defines whether monitoring thresholds are specified as absolute measured values, percentages of a nominal value or another manufacturer-defined reference.

Relay Operate Timems

Manufacturer-declared time from application of the control signal until the relay reaches its operated switching state.

Relay Release Timems

Manufacturer-declared time from removal of the control signal until the relay returns to its released switching state.

Contact Bounce Timems

Manufacturer-declared duration of mechanical contact bounce following relay contact operation.

Relay Contact Structure

Mechanical structure of an individual switching contact system, for example single, double or bifurcated contact.

Relay Contact Material

Electrical contact material or contact-material system used by the relay switching contacts.

Relay Contact Maximum Switching VoltageV

Maximum manufacturer-declared voltage that may be switched by the relay-output contacts.

Relay Contact Maximum Switching CurrentA

Maximum manufacturer-declared current that may be switched by the relay-output contacts.

Relay Contact Minimum Switching VoltageV

Minimum manufacturer-declared switching voltage for reliable operation of the relay contact.

Relay Contact Minimum Switching CurrentA

Minimum manufacturer-declared switching current for reliable relay-contact operation.

Relay Contact Limiting Continuous CurrentA

Maximum continuous current permitted through a closed relay contact under the manufacturer-declared conditions.

Relay Contact Maximum Inrush CurrentA

Maximum short-duration inrush current permitted through the relay switching contact.

Relay Contact Maximum AC Switching VoltageV

Maximum AC switching voltage of the relay output contact.

Relay Contact Maximum DC Switching VoltageV

Maximum DC switching voltage of the relay output contact.

Number of Phases

Number of phases of the electrical system for which the product is designed to be connected or used.

Conductor System

Configuration of live and neutral conductors of the electrical system supported by the product.

Current Measurement Supported

Indicates whether the product can measure and provide electrical current values.

Minimum Current Measurement RangeA

Lowest current that can be measured or monitored within the manufacturer-declared measuring range.

Maximum Current Measurement RangeA

Highest current that can be measured or monitored within the manufacturer-declared measuring range.

Current Transformer Input Supported

Indicates that the measuring circuit supports connection through an external current transformer.

Configurable Current Transformer Ratio

Indicates that the current transformer ratio used for measurement scaling can be configured in the device.

Minimum Current Transformer Primary Current SettingA

Minimum configurable primary current value used for current transformer scaling.

Maximum Current Transformer Primary Current SettingA

Maximum configurable primary current value used for current transformer scaling.

Supported Current Transformer Secondary Currents

Standard secondary current ratings of external current transformers supported by the measuring input.

Current Measuring Input Short-Time OverloadA

Maximum short-duration current that the measuring input can withstand without damage under manufacturer-declared conditions.

Current Measuring Input Short-Time Overload Durations

Maximum duration associated with the declared short-time current overload capability of the measuring input.

Current Measuring Input Continuous OverloadA

Maximum current that may be continuously applied to the measuring input without damage under manufacturer-declared conditions.

Minimum / Maximum Measurement Supported

Indicates whether the product stores or provides minimum and maximum values of measured quantities.

Adjustable Current Monitoring Threshold

Indicates that one or more current monitoring thresholds can be adjusted by the user.

Maximum Current Fault Detection Times

Maximum intrinsic detection time for an overcurrent or undercurrent condition, excluding an intentionally configured response delay.

Minimum Overcurrent ThresholdA

Minimum configurable absolute current threshold for overcurrent monitoring.

Maximum Overcurrent ThresholdA

Maximum configurable absolute current threshold for overcurrent monitoring.

Minimum Relative Overcurrent Threshold%

Minimum configurable overcurrent threshold expressed relative to the applicable nominal or reference current.

Maximum Relative Overcurrent Threshold%

Maximum configurable overcurrent threshold expressed relative to the applicable nominal or reference current.

Connection Point Count

Total number of electrical connection points provided by the product.

Minimum Conductor Cross-Sectionmm²

Minimum conductor cross-section permitted by the connection system within its general conductor-size range.

Maximum Conductor Cross-Sectionmm²

Maximum conductor cross-section permitted by the connection system within its general conductor-size range.

Minimum Rigid Conductor Cross-Sectionmm²

Minimum rigid conductor cross-section permitted by an electrically and mechanically equivalent connection point.

Maximum Rigid Conductor Cross-Sectionmm²

Maximum rigid conductor cross-section permitted by an electrically and mechanically equivalent connection point.

Minimum Flexible Conductor Cross-Sectionmm²

Minimum flexible conductor cross-section permitted by the relevant connection point.

Maximum Flexible Conductor Cross-Sectionmm²

Maximum flexible conductor cross-section permitted by the relevant connection point.

Minimum Ferrule Cross-Section without Sleevemm²

Minimum flexible conductor cross-section with a ferrule without an insulating plastic collar permitted by the relevant connection point.

Maximum Ferrule Cross-Section without Sleevemm²

Maximum flexible conductor cross-section with a ferrule without an insulating plastic collar permitted by the relevant connection point.

Minimum Ferrule Cross-Section with Sleevemm²

Minimum flexible conductor cross-section with a ferrule and insulating plastic collar permitted by the relevant connection point.

Maximum Ferrule Cross-Section with Sleevemm²

Maximum flexible conductor cross-section with a ferrule and insulating plastic collar permitted by the relevant connection point.

Minimum TWIN Ferrule Conductor Cross-Sectionmm²

Minimum cross-section of each of two conductors connected simultaneously using a TWIN ferrule.

Maximum TWIN Ferrule Conductor Cross-Sectionmm²

Maximum cross-section of each of two conductors connected simultaneously using a TWIN ferrule.

Minimum Stripping Lengthmm

Minimum conductor stripping length specified by the manufacturer.

Maximum Stripping Lengthmm

Maximum conductor stripping length specified by the manufacturer.

Minimum Direct-Pluggable Rigid Conductor Cross-Sectionmm²

Minimum rigid conductor cross-section suitable for direct insertion into a compatible connection without prior actuation of the release mechanism.

Maximum Direct-Pluggable Rigid Conductor Cross-Sectionmm²

Maximum rigid conductor cross-section suitable for direct insertion into a compatible connection without prior actuation of the release mechanism.

Minimum Direct-Pluggable Ferrule Cross-Section without Sleevemm²

Minimum conductor cross-section with a ferrule without an insulating plastic collar suitable for direct insertion into a compatible connection.

Maximum Direct-Pluggable Ferrule Cross-Section without Sleevemm²

Maximum conductor cross-section with a ferrule without an insulating plastic collar suitable for direct insertion into a compatible connection.

Minimum Direct-Pluggable Ferrule Cross-Section with Sleevemm²

Minimum conductor cross-section with a ferrule and insulating plastic collar suitable for direct insertion into a compatible connection.

Maximum Direct-Pluggable Ferrule Cross-Section with Sleevemm²

Maximum conductor cross-section with a ferrule and insulating plastic collar suitable for direct insertion into a compatible connection.

Connection Actuation Type

Method or operator action used to open, actuate, or prepare the clamping mechanism before conductor insertion.

Conductor Release Method

Method used to release and remove a connected conductor from the connection point.

Direct Conductor Insertion Supported

Indicates whether an applicable conductor can be inserted directly without first opening the clamping mechanism using a tool or actuator.

Tool-Free Conductor Connection

Indicates whether normal conductor connection can be performed without using a separate hand tool.

Visual Connection Feedback

Indicates whether visual feedback is provided to confirm correct conductor connection or the intended operating state of the clamping mechanism.

Haptic Connection Feedback

Indicates whether haptic feedback is provided to confirm correct conductor connection or attainment of the intended operating state by the mechanism.

Conductor Release Tool Required

Indicates whether a separate tool is required to release the connected conductor.

Conductor Release Tool Type

Type, size, or designation of the tool declared by the manufacturer for actuating the conductor-release mechanism.

Terminal Screw Thread

Thread designation of the screw used in the conductor clamping mechanism, for example M2.5, M3, M4, or another manufacturer-declared designation.

Terminal Screw Head Type

Drive geometry of the screw head used to clamp the conductor in the terminal block.

Terminal Screwdriver Size

Size or designation of the screwdriver, bit, or other tool required to operate the terminal screw.

Minimum Terminal Tightening TorqueNm

Minimum tightening torque of the terminal screw, bolt, or nut declared by the manufacturer where a permissible range is specified.

Maximum Terminal Tightening TorqueNm

Maximum tightening torque of the terminal screw, bolt, or nut declared by the manufacturer where a permissible range is specified.

Minimum Cross-Section for Two Equal Rigid Conductorsmm²

Minimum cross-section of each of two equal rigid conductors that may be connected simultaneously to one clamping point.

Maximum Cross-Section for Two Equal Rigid Conductorsmm²

Maximum cross-section of each of two equal rigid conductors that may be connected simultaneously to one clamping point.

Minimum Cross-Section for Two Equal Flexible Conductorsmm²

Minimum cross-section of each of two equal flexible conductors that may be connected simultaneously to one clamping point.

Maximum Cross-Section for Two Equal Flexible Conductorsmm²

Maximum cross-section of each of two equal flexible conductors that may be connected simultaneously to one clamping point.

Minimum Cross-Section for Two Equal Conductors with Ferrules without Sleevesmm²

Minimum cross-section of each of two equal flexible conductors fitted with separate ferrules without insulating collars and permitted for joint connection to one clamping point.

Maximum Cross-Section for Two Equal Conductors with Ferrules without Sleevesmm²

Maximum cross-section of each of two equal flexible conductors fitted with separate ferrules without insulating collars and permitted for joint connection to one clamping point.

Protection and Safety8
Halogen-Free

Indicates whether the product material is classified as halogen-free according to the characteristics declared by the manufacturer.

IP Rating

Degree of enclosure protection against access to hazardous parts and ingress of solid objects and water, designated by the IP code.

IK Rating

Class of enclosure resistance to external mechanical impacts designated by the IK code.

Protection Against Direct Contact

Method or level of protection of the user against direct contact with hazardous live parts.

Finger-Safe

Indicates whether the design prevents finger access to hazardous live parts in the intended condition.

Touch-Safe

Indicates whether the design provides protection against accidental contact with hazardous live parts.

Flammability Class

Classification of a material according to its ability to ignite, sustain combustion, and cease burning under a specified test.

Glow-Wire Test Temperature°C

Temperature of the heated wire used when testing the material or product against an ignition source.

Environmental Conditions18
Minimum Operating Temperature°C

Minimum ambient temperature at which normal operation of the product is permitted.

Maximum Operating Temperature°C

Maximum ambient temperature at which normal operation of the product is permitted.

Maximum 24-Hour Average Temperature°C

Maximum permissible average ambient temperature over a consecutive 24-hour period.

Minimum Storage Temperature°C

Minimum ambient temperature permitted during storage of the product while not in operation.

Maximum Storage Temperature°C

Maximum ambient temperature permitted during storage of the product while not in operation.

Minimum Transport Temperature°C

Minimum ambient temperature permitted during transportation of the product.

Maximum Transport Temperature°C

Maximum ambient temperature permitted during transportation of the product.

Temperature Derating Required

Indicates whether permissible electrical or thermal loading must be reduced as temperature changes.

Temperature Derating Start°C

Temperature above which the permissible product load must be reduced.

Temperature Derating Curve Available

Indicates whether the manufacturer has published the relationship between permissible product load and temperature.

Minimum Relative Humidity%

Minimum relative air humidity permitted for the declared operating or test condition.

Maximum Relative Humidity%

Maximum relative air humidity permitted for the declared operating or test condition.

Non-Condensing Humidity

Indicates whether the permissible humidity value applies only to non-condensing conditions.

Maximum Installation Altitudem

Maximum altitude above sea level at which the product may be installed without exceeding the declared conditions.

Altitude Derating Required

Indicates whether the permissible product load must be reduced as installation altitude increases.

Altitude Derating Startm

Altitude above sea level above which the permissible product load must be reduced.

Vibration Resistant

Indicates whether the product's resistance to vibration has been verified under the declared conditions.

Mechanical Shock Resistant

Indicates whether the product's resistance to short-duration mechanical shocks has been verified.

Included Equipment9
Documentation Included

Indicates whether documentation is included in the product's standard supply.

Local HMI Present

Indicates whether a local human-machine interface (HMI) is provided for monitoring, configuration, or control.

Display Present

Indicates whether the product has an integrated local display.

Display Type

Technology or construction type of the product's integrated display.

Display Backlight

Indicates whether the integrated display has a backlight.

Status LED Count

Number of integrated LEDs used to indicate product status or operating modes.

Event Log Supported

Indicates whether the product can store an internal event log.

Event Log Capacityevents

Maximum number of event records that can be stored in the product's internal log.

Real-Time Clock Present

Indicates whether an integrated real-time clock is provided for timekeeping, event time-stamping, or time-based functions.

Special Features30
Measured Value Memory Supported

Indicates whether one or more measured values can be stored, for example the latest, minimum, maximum, or a value associated with a fault event.

Fault Memory Supported

Indicates whether information about a fault condition, alarm, or protective operation can be retained after the cause of the event has disappeared.

Fault Memory Configurable

Indicates whether the mode of storing or latching a fault condition can be configured.

Automatic Reset Supported

Indicates whether an alarm or output state can automatically return to normal after the operating cause disappears, according to the product settings.

Adjustable Start-Up Delay

Indicates whether the delay can be adjusted during which a monitoring or protective function temporarily ignores the monitored condition after power-up or start.

Minimum Start-Up Delays

Minimum available setting of the start-up delay for the monitoring or protective function.

Maximum Start-Up Delays

Maximum available setting of the start-up delay for the monitoring or protective function.

Adjustable Release Delay

Indicates whether the delay before an alarm or output state returns after the operating condition disappears can be adjusted.

Minimum Release Delays

Minimum available setting of the release delay for the alarm or output state.

Maximum Release Delays

Maximum available setting of the release delay for the alarm or output state.

Adjustable Switching Hysteresis

Indicates whether the hysteresis between the operating threshold and release threshold can be adjusted.

Minimum Switching Hysteresis%

Minimum available setting of switching or alarm hysteresis relative to the corresponding threshold.

Maximum Switching Hysteresis%

Maximum available setting of switching or alarm hysteresis relative to the corresponding threshold.

External Test Input Supported

Indicates whether an external wired input or external push-button is supported for initiating the specified TEST function.

External Reset Input Supported

Indicates whether an external wired input or external push-button is supported for performing the specified RESET function.

Parameter Lock Supported

Indicates whether product settings can be protected against unauthorized modification by means of a specified mechanical, software, or password-based locking mechanism.

Test Button Present

Indicates whether the product has a local TEST button for the specified functional check of the device.

Reset Button Present

Indicates whether the product has a separate local RESET button for performing the specified reset function.

Status Indicator Present

Indicates whether the product has a local visual or mechanical indicator of operating, fault, or end-of-life status.

Status Indicator Types

Types of local visual or mechanical status indication provided by the product design.

Monitoring Function Configurable

Indicates that the principal monitoring function can be selected or configured on the product, for example over-value, under-value or window monitoring.

Monitoring Threshold Setting Method

Methods available for setting monitoring or switching threshold values.

Adjustable Monitoring Trip Delay

Indicates that the delay between detection of the monitored fault condition and switching of the monitoring output can be adjusted.

Minimum Monitoring Trip Delays

Minimum configurable delay between detection of a monitored fault condition and output switching.

Maximum Monitoring Trip Delays

Maximum configurable delay between detection of a monitored fault condition and output switching.

Monitoring Trip Delay Mode

Timing behaviour of the monitoring relay output with respect to appearance or disappearance of the monitored condition.

Monitoring Output Principle Configurable

Indicates that the monitoring output can be configured between supported operating principles.

Automatic Current Type Detection

Indicates that the measuring input automatically distinguishes between AC and DC current without manual selection.

Current Monitoring Functions

Current supervision functions supported by the device.

External Shunt Measurement Supported

Indicates that current can be monitored using an external measuring shunt.

Standards and Compliance21
Conformity Regions

Regions or markets for which the manufacturer declares regulatory or certification compliance of the product.

Certification and Conformity Marks

Certification, market-approval, or conformity marks applicable to the product.

Primary Product Standard

Primary normative document or standard according to which the manufacturer classifies or assesses the product.

Additional Standards

Additional normative documents and standards declared by the manufacturer as applicable to the product.

Declaration of Conformity Available

Indicates whether an official declaration of conformity is available for the product.

Certificate Available

Indicates whether a certificate relating to the declared certification or conformity of the product is available.

Certificate Number

Identification number of the certificate relating to the product or its certified version.

Certification Body

Name of the organization that issued the certificate or performed the relevant conformity assessment.

Third-Party Tested

Indicates whether the product was tested by an organization independent of the manufacturer.

CE Marked

Indicates whether the CE marking is applied to the product where applicable.

UKCA Marked

Indicates whether the UKCA marking is applied to the product where applicable.

EAC Marked

Indicates whether the EAC marking is applied to the product where applicable.

UL Listed

Indicates whether the product has a declared UL Listed certification or recognition status.

UL Recognized

Indicates whether the product has a declared UL Recognized certification or recognition status.

cULus Marked

Indicates whether the cULus mark is applied to the product where applicable.

CSA Certified

Indicates whether the product has a declared CSA certification or recognition status.

TÜV Certified

Indicates whether the product has a declared TÜV certification or recognition status.

VDE Certified

Indicates whether the product has a declared VDE certification or recognition status.

RoHS Compliant

Indicates whether product compliance with applicable RoHS restrictions on hazardous substances has been declared.

REACH Compliant

Indicates whether the manufacturer declares compliance of the product with applicable REACH Regulation requirements.

WEEE Applicable

Indicates whether the product falls within the scope of WEEE requirements for waste electrical and electronic equipment.

Logistics10
Net Weightkg

Mass of the product itself, excluding transport packaging, additional accessories, and external equipment.

Gross Weightkg

Mass of the product together with its individual packaging and the accessories included in it.

Package Widthmm

External horizontal dimension of the product's individual package.

Package Heightmm

External vertical dimension of the product's individual package.

Package Depthmm

External depth dimension of the product's individual package.

Packaging Type

Design type of the product's individual or transport packaging.

Units per Package

Number of individual products contained in one packaging unit at the specified level.