Device description

Motor Protection Relay

Multifunction protective relay for monitoring electrical and thermal conditions of a motor.

A motor protection relay combines multiple protective functions based on current, voltage, thermal measurements, or sensor inputs.

Depending on design it may provide overload protection, current unbalance and phase loss, stall, jam, locked rotor, excessive start time, thermistor protection, and other functions.

Advanced devices may provide alarms, trip history, diagnostics, control I/O, and communication with automation systems.

Selection considers motor type and power, measurement range, required protective functions, sensor interfaces, communication, and the method used to trip or stop the motor.

Components in this subcategory

Motor protection relays for industrial drives and motor-starting systems.

Available parameters

Motor Protection Relay

284 parameters
Dimensions4
Widthmm

External horizontal dimension of the product between its outermost lateral points.

Heightmm

External vertical dimension of the product from its lowest to its highest point.

Depthmm

External distance between the foremost and rearmost surfaces of the product.

Net Weightkg

Mass of the product itself, excluding transport packaging, additional accessories, and external equipment.

Materials and Finish7
Material

Primary material from which the product is manufactured.

Material Grade

Grade, alloy, class, or technical designation of the product's primary material.

Color

Primary visually perceived colour of the product's external surface.

RAL Color

Designation of the product's primary surface colour according to the RAL colour system.

Surface Finish

Type of final surface finish of the product determining its appearance and service properties.

Surface Treatment

Technological surface treatment applied to modify its protective, mechanical, or decorative properties.

Coating Type

Type of protective, functional, or decorative coating applied to the surface.

Mounting and Installation23
Mounting Type

Installation arrangement permitted by the product design, such as wall-mounted, flush-mounted, floor-mounted, or another specified mounting type.

Mounting Method

Method used to mechanically secure the product to a support, surface, or load-bearing structure.

Mounting Surface

Type of surface or supporting base to which the product may be fixed.

Orientation

Permissible spatial orientation of the component during installation and operation.

Number of Mounting Holes

Number of holes provided in the product for mechanical fixing.

Mounting Hole Diametermm

Diameter of the hole provided for a fixing element used when mounting the product.

Horizontal Mounting Hole Spacingmm

Distance between the centres of mounting holes in the horizontal direction.

Vertical Mounting Hole Spacingmm

Distance between the centres of mounting holes in the vertical direction.

Mounting Pattern Widthmm

Horizontal dimension of the mounting pattern between the outermost fixing points of the product.

Mounting Pattern Heightmm

Vertical dimension of the mounting pattern between the outermost fixing points of the product.

Mounting Screw Size

Size designation of the screw, bolt, or other threaded fastener used for mounting the product.

Mounting Thread

Designation of the thread provided in the product's mounting holes or fixing elements.

Mounting Tightening TorqueNm

Tightening torque recommended or permitted for fasteners during product installation.

Fasteners Included

Indicates whether the required fasteners are included with the product.

DIN Rail Mounting Supported

Indicates whether the design provides for mounting equipment on a DIN rail.

Direct Device Mounting Supported

Indicates whether equipment may be mounted directly to the mounting surface without an intermediate DIN rail.

Required Top Installation Clearancemm

Minimum free space required above the product for installation, cooling, or servicing.

Required Bottom Installation Clearancemm

Minimum free space required below the product for installation, cooling, or servicing.

Required Left Installation Clearancemm

Minimum free space required to the left of the product for installation or servicing.

Required Right Installation Clearancemm

Minimum free space required to the right of the product for installation or servicing.

Required Front Installation Clearancemm

Minimum free space required in front of the product for installation and normal operation.

Required Rear Installation Clearancemm

Minimum free space required behind the product for installation and normal operation.

Maximum Mounting Tilt Angle°

Maximum angle permitted by the manufacturer by which the product may deviate from the specified reference orientation during installation.

Electrical Parameters48
Supply Current Type

Type of electrical current for which the product's main supply circuit is intended.

Rated VoltageV

Voltage value assigned to the product by the manufacturer for specified application conditions and characteristics.

Rated Operational VoltageV

Operating-circuit voltage with reference to which the product's performance characteristics are specified.

Minimum Operating VoltageV

Minimum voltage at which the manufacturer guarantees the intended operating mode of the product.

Maximum Operating VoltageV

Maximum voltage at which continuous operation of the product is permitted under the conditions declared by the manufacturer.

Rated FrequencyHz

AC frequency assigned to the product for normal operating conditions.

Minimum FrequencyHz

Lower limit of the electrical network or signal frequency at which product operation is permitted.

Maximum FrequencyHz

Upper limit of the electrical network or signal frequency at which product operation is permitted.

Rated CurrentA

Current assigned to the product by the manufacturer for the declared operating and thermal conditions.

Continuous Service CurrentA

Current that the product can carry continuously under the manufacturer's declared conditions without exceeding permissible temperature rise.

Rated Insulation VoltageV

Voltage with reference to which the product's insulation clearances and dielectric properties are specified.

Rated Impulse Withstand VoltagekV

Peak value of an impulse voltage of specified waveform that the product insulation must withstand without breakdown.

Dielectric Test VoltageV

Test voltage applied to verify the dielectric strength of the product insulation.

Minimum Insulation ResistanceMΩ

Minimum permissible insulation resistance between the specified electrically separated parts.

Overvoltage Category

Category characterizing the expected level of impulse overvoltages at the product's point of use.

Pollution Degree

Degree of pollution of the surrounding microenvironment considered when selecting insulation distances and product characteristics.

Electrical Protection Class

Class of protection against electric shock determined by the product design and protective connection method.

Supported Motor Types

Motor technologies and motor types that the product is designed to control, start, protect or drive.

Supported Motor Phase Configurations

Electrical phase configurations of motors supported by the product.

Supported Motor Winding Connections

Motor winding connection configurations supported by the product.

Minimum Supported Motor Rated VoltageV

Minimum motor rated voltage supported by the product.

Maximum Supported Motor Rated VoltageV

Maximum motor rated voltage supported by the product.

Minimum Supported Motor Rated CurrentA

Minimum motor rated current supported by the product.

Maximum Supported Motor Rated CurrentA

Maximum motor rated current supported by the product.

Minimum Supported Motor Rated PowerW

Minimum motor rated power supported by the product.

Maximum Supported Motor Rated PowerW

Maximum motor rated power supported by the product.

Minimum Supported Motor Rated FrequencyHz

Minimum motor rated frequency supported by the product.

Maximum Supported Motor Rated FrequencyHz

Maximum motor rated frequency supported by the product.

Minimum Supported Motor Rated Speedrpm

Minimum motor rated rotational speed supported by the product.

Maximum Supported Motor Rated Speedrpm

Maximum motor rated rotational speed supported by the product.

Minimum Supported Motor Pole Count

Minimum number of motor poles supported by the product.

Maximum Supported Motor Pole Count

Maximum number of motor poles supported by the product.

Minimum Supported Motor Service Factor

Minimum motor service factor supported or configurable for motor protection or control.

Maximum Supported Motor Service Factor

Maximum motor service factor supported or configurable for motor protection or control.

Minimum Current Measurement RangeA

Lowest current that can be measured or monitored within the manufacturer-declared measuring range.

Maximum Current Measurement RangeA

Highest current that can be measured or monitored within the manufacturer-declared measuring range.

Current Measurement Connection Method

Supported methods for connecting the monitored current to the measuring device.

Current Transformer Input Supported

Indicates that the measuring circuit supports connection through an external current transformer.

Configurable Current Transformer Ratio

Indicates that the current transformer ratio used for measurement scaling can be configured in the device.

Minimum Current Transformer Primary Current SettingA

Minimum configurable primary current value used for current transformer scaling.

Maximum Current Transformer Primary Current SettingA

Maximum configurable primary current value used for current transformer scaling.

Supported Current Transformer Secondary Currents

Standard secondary current ratings of external current transformers supported by the measuring input.

Relay Contact Maximum Switching VoltageV

Maximum manufacturer-declared voltage that may be switched by the relay-output contacts.

Relay Contact Maximum Switching CurrentA

Maximum manufacturer-declared current that may be switched by the relay-output contacts.

Relay Contact Maximum Switching PowerW

Maximum manufacturer-declared active power that may be switched by the relay-output contacts.

Measurement Accuracy%

Manufacturer-declared accuracy of the measured value under the specified reference conditions.

Threshold Setting Accuracy%

Manufacturer-declared accuracy or tolerance of the configured monitoring threshold.

Repeat Accuracy%

Manufacturer-declared repeatability of switching, alarm or monitoring operation under unchanged reference conditions.

Protection and Safety97
IP Rating

Degree of enclosure protection against access to hazardous parts and ingress of solid objects and water, designated by the IP code.

Front-Side IP Rating

IP degree of protection provided by the accessible front side of the product after its intended installation.

IK Rating

Class of enclosure resistance to external mechanical impacts designated by the IK code.

Ingress Protection Certified

Indicates whether the declared ingress protection of the enclosure has been verified by certification or testing.

Protection Against Direct Contact

Method or level of protection of the user against direct contact with hazardous live parts.

Minimum Overload Current SettingA

Minimum adjustable overload current setting.

Maximum Overload Current SettingA

Maximum adjustable overload current setting.

Overload Current Setting StepA

Smallest selectable increment of the overload current setting.

Supported Overload Trip Classes

Standardized overload-relay trip classes supported or selectable by the product.

Minimum Trip Time at 7.2 × Overload Settings

Minimum declared trip time from the applicable initial condition at 7.2 times the overload current setting.

Maximum Trip Time at 7.2 × Overload Settings

Maximum declared trip time from the applicable initial condition at 7.2 times the overload current setting.

Overload Temperature Compensation Supported

Indicates that overload tripping characteristics are compensated for ambient temperature.

Minimum Overload Compensation Temperature°C

Minimum ambient temperature within the declared overload temperature-compensation range.

Maximum Overload Compensation Temperature°C

Maximum ambient temperature within the declared overload temperature-compensation range.

Motor Phase-Loss Sensitivity Supported

Indicates that the motor overload protection characteristic is specifically sensitive to single-phasing or phase-loss conditions through motor-current imbalance or an equivalent protection principle.

Protection Functions

Set of protection functions integrated into the product or provided by it in its normal intended configuration.

Supported Reset Modes

Reset or restart modes supported after the condition that caused a trip, protection action, alarm or safety stop has been cleared.

Test Button Present

Indicates whether the product has a local TEST button for the specified functional check of the device.

Trip Indicator Present

Indicates whether a local mechanical or electronic indicator shows that the circuit breaker has tripped protectively.

Minimum Current Unbalance Trip Threshold%

Minimum configurable motor phase-current unbalance threshold that can initiate protection.

Maximum Current Unbalance Trip Threshold%

Maximum configurable motor phase-current unbalance threshold that can initiate protection.

Minimum Current Unbalance Trip Delays

Minimum configurable delay before tripping on excessive motor current unbalance.

Maximum Current Unbalance Trip Delays

Maximum configurable delay before tripping on excessive motor current unbalance.

Minimum Stall Pickup Ratio%

Minimum configurable stall-protection current threshold expressed as a percentage of the relevant motor-current reference.

Maximum Stall Pickup Ratio%

Maximum configurable stall-protection current threshold expressed as a percentage of the relevant motor-current reference.

Minimum Stall Trip Delays

Minimum configurable delay before a detected motor stall causes a protective trip.

Maximum Stall Trip Delays

Maximum configurable delay before a detected motor stall causes a protective trip.

Minimum Jam Pickup Ratio%

Minimum configurable current threshold for motor jam protection.

Maximum Jam Pickup Ratio%

Maximum configurable current threshold for motor jam protection.

Minimum Jam Trip Delays

Minimum configurable delay before a detected motor jam causes a protective trip.

Maximum Jam Trip Delays

Maximum configurable delay before a detected motor jam causes a protective trip.

Minimum Locked-Rotor Pickup Ratio%

Minimum configurable current threshold for locked-rotor protection.

Maximum Locked-Rotor Pickup Ratio%

Maximum configurable current threshold for locked-rotor protection.

Minimum Locked-Rotor Trip Delays

Minimum configurable delay before locked-rotor protection trips.

Maximum Locked-Rotor Trip Delays

Maximum configurable delay before locked-rotor protection trips.

Minimum Start Time Supervision Settings

Minimum configurable maximum permitted motor starting time.

Maximum Start Time Supervision Settings

Maximum configurable maximum permitted motor starting time.

Maximum Starts per Hour

Maximum permitted or configurable number of motor starts within one hour.

Motor Thermal Model Supported

Indicates that motor thermal state is calculated using an internal thermal model.

Motor Thermal Capacity Reporting Supported

Indicates that calculated motor thermal-capacity utilization can be displayed, communicated or otherwise reported.

Motor Thermal Capacity Alarm Threshold%

Configurable motor thermal-capacity utilization level at which a warning or alarm is generated.

Minimum Motor Heating Time Constants

Minimum configurable motor heating time constant used by the thermal model.

Maximum Motor Heating Time Constants

Maximum configurable motor heating time constant used by the thermal model.

Minimum Motor Cooling Time Constants

Minimum configurable motor cooling time constant used by the thermal model.

Maximum Motor Cooling Time Constants

Maximum configurable motor cooling time constant used by the thermal model.

Motor Restart Inhibit after Trip Supported

Indicates that motor restart can be inhibited after a protection trip until defined restart conditions are satisfied.

Minimum Motor Restart Inhibit Times

Minimum configurable restart-inhibit time after a motor protection trip.

Maximum Motor Restart Inhibit Times

Maximum configurable restart-inhibit time after a motor protection trip.

Thermal Memory Supported

Indicates whether thermal memory is used by the overload protection algorithm.

Adjustable Current Monitoring Threshold

Indicates that one or more current monitoring thresholds can be adjusted by the user.

Minimum Undercurrent ThresholdA

Minimum configurable absolute current threshold for undercurrent monitoring.

Maximum Undercurrent ThresholdA

Maximum configurable absolute current threshold for undercurrent monitoring.

Minimum Relative Undercurrent Threshold%

Minimum configurable undercurrent threshold expressed relative to the applicable nominal or reference current.

Maximum Relative Undercurrent Threshold%

Maximum configurable undercurrent threshold expressed relative to the applicable nominal or reference current.

Maximum Current Fault Detection Times

Maximum intrinsic detection time for an overcurrent or undercurrent condition, excluding an intentionally configured response delay.

Minimum Voltage Unbalance Threshold%

Minimum configurable voltage unbalance or phase asymmetry threshold.

Maximum Voltage Unbalance Threshold%

Maximum configurable voltage unbalance or phase asymmetry threshold.

Phase Loss Detection Threshold Ratio%

Voltage level relative to the nominal or reference voltage below which a phase is considered lost.

Maximum Regenerative Feedback for Phase Loss Detection%

Maximum regenerated or feedback voltage relative to the normal phase voltage at which reliable phase loss detection is manufacturer-declared.

Maximum Phase Loss Detection Times

Maximum intrinsic time required to detect loss of a monitored phase.

Adjustable Ground-Fault Pickup

Indicates whether the ground-fault protection pickup threshold can be adjusted.

Minimum Ground-Fault Pickup Ratio

Minimum supported ground-fault protection pickup setting, expressed as a multiple of the selected reference current.

Maximum Ground-Fault Pickup Ratio

Maximum supported ground-fault protection pickup setting, expressed as a multiple of the selected reference current.

Minimum Ground-Fault Pickup CurrentA

Minimum supported absolute ground-fault protection pickup current when the setting is specified directly in amperes.

Maximum Ground-Fault Pickup CurrentA

Maximum supported absolute ground-fault protection pickup current when the setting is specified directly in amperes.

Ground-Fault Pickup Reference

Reference current relative to which the ground-fault protection pickup ratio is defined.

Adjustable Ground-Fault Delay

Indicates whether the ground-fault protection delay can be adjusted.

Minimum Ground-Fault Delay Settings

Minimum available ground-fault protection delay setting.

Maximum Ground-Fault Delay Settings

Maximum available ground-fault protection delay setting.

Ground-Fault Delay Reference Current Multiple

Multiple of the reference current at which the inverse-time ground-fault protection delay is specified, where applicable.

Ground-Fault Curve Modes

Supported timing characteristic modes of ground-fault protection.

Ground-Fault Protection Disable Supported

Indicates whether the ground-fault protection function can be disabled.

Ground-Fault Sensing Methods

Current-sensing methods supported for ground-fault or earth-fault protection, such as residual summation of phase currents or a dedicated core-balance current transformer.

Core-Balance Current Transformer Input Supported

Indicates that the protection device supports a dedicated core-balance or zero-sequence current transformer input for earth-fault measurement.

Zero-Sequence Current Measurement Supported

Indicates that zero-sequence or residual current is measured or calculated and available as a measured value.

Minimum Zero-Sequence Current MeasurementA

Lower limit of the manufacturer-declared zero-sequence or residual-current measurement range.

Maximum Zero-Sequence Current MeasurementA

Upper limit of the manufacturer-declared zero-sequence or residual-current measurement range.

Negative-Sequence Current Measurement Supported

Indicates that negative-sequence current is calculated or measured and available to the protection or monitoring functions.

Negative-Sequence Current Ratio Measurement Supported

Indicates that negative-sequence current can be reported relative to positive-sequence, phase or motor rated current.

Minimum Negative-Sequence Current Trip Threshold%

Minimum configurable negative-sequence current protection threshold expressed as a percentage of the applicable current reference.

Maximum Negative-Sequence Current Trip Threshold%

Maximum configurable negative-sequence current protection threshold expressed as a percentage of the applicable current reference.

Minimum Negative-Sequence Current Trip Delays

Minimum configurable operating delay of the negative-sequence current protection function.

Maximum Negative-Sequence Current Trip Delays

Maximum configurable operating delay of the negative-sequence current protection function.

Minimum Motor Load Alarm Threshold%

Minimum configurable motor-load threshold used for underload, overload or process-load alarming.

Maximum Motor Load Alarm Threshold%

Maximum configurable motor-load threshold used for underload, overload or process-load alarming.

Protection Functions Individually Configurable

Indicates that individual protection functions can be independently enabled, disabled or configured.

Protection Function Action Assignment Supported

Indicates that the response of individual protection functions can be configured, for example as warning, alarm, trip or inhibit.

Protection Pre-Trip Alarm Supported

Indicates that one or more protection functions can generate a warning or pre-alarm before the final trip threshold is reached.

Thermistor Sensor Circuit Count

Number of independent thermistor sensor circuits evaluated by the protection relay.

Thermistor Trip ResistanceΩ

Sensor-circuit resistance at which the thermistor protection relay changes to the trip or overtemperature state.

Thermistor Reset ResistanceΩ

Sensor-circuit resistance below which reset or return from the thermistor trip state becomes possible.

Thermistor Short-Circuit Resistance ThresholdΩ

Sensor-circuit resistance below which the thermistor input is interpreted as a short circuit.

Maximum Thermistor Sensor Loop ResistanceΩ

Maximum permissible total cold-state resistance of the connected thermistor sensor circuit.

Maximum PTC Sensors in Series

Maximum number of PTC thermistor sensors permitted in series in one sensor circuit where declared by the manufacturer.

Thermistor Warning Circuit Supported

Indicates support for a separate thermistor warning or pre-alarm sensor circuit in addition to the trip circuit.

Thermistor Warning Resistance ThresholdΩ

Sensor-circuit resistance corresponding to operation of the thermistor warning or pre-alarm function.

Motor Winding Temperature Monitoring Supported

Indicates suitability for direct thermal monitoring of motor or generator windings using embedded temperature sensors.

Environmental Conditions19
Minimum Operating Temperature°C

Minimum ambient temperature at which normal operation of the product is permitted.

Maximum Operating Temperature°C

Maximum ambient temperature at which normal operation of the product is permitted.

Minimum Storage Temperature°C

Minimum ambient temperature permitted during storage of the product while not in operation.

Maximum Storage Temperature°C

Maximum ambient temperature permitted during storage of the product while not in operation.

Minimum Relative Humidity%

Minimum relative air humidity permitted for the declared operating or test condition.

Maximum Relative Humidity%

Maximum relative air humidity permitted for the declared operating or test condition.

Relative Humidity Reference Temperature°C

Temperature at which the corresponding relative humidity value is specified or standardized.

Humidity Condition

Nature of the humidity conditions for which product operation or resistance is declared.

Non-Condensing Humidity

Indicates whether the permissible humidity value applies only to non-condensing conditions.

Maximum Installation Altitudem

Maximum altitude above sea level at which the product may be installed without exceeding the declared conditions.

Altitude Derating Required

Indicates whether the permissible product load must be reduced as installation altitude increases.

Altitude Derating Startm

Altitude above sea level above which the permissible product load must be reduced.

Vibration Resistant

Indicates whether the product's resistance to vibration has been verified under the declared conditions.

Minimum Vibration FrequencyHz

Lower limit of vibration frequency applied or permitted in the relevant test.

Maximum Vibration FrequencyHz

Upper limit of vibration frequency applied or permitted in the relevant test.

Vibration Accelerationm/s²

Amplitude or test-method-specified acceleration of vibration applied during product testing.

Mechanical Shock Resistant

Indicates whether the product's resistance to short-duration mechanical shocks has been verified.

Shock Accelerationm/s²

Maximum acceleration generated during mechanical shock testing of the product.

Shock Durationms

Duration of an individual mechanical shock pulse during product testing.

Included Equipment5
Local HMI Present

Indicates whether a local human-machine interface (HMI) is provided for monitoring, configuration, or control.

Display Present

Indicates whether the product has an integrated local display.

Display Type

Technology or construction type of the product's integrated display.

Display Backlight

Indicates whether the integrated display has a backlight.

Status LED Count

Number of integrated LEDs used to indicate product status or operating modes.

Special Features60
Current Unbalance Measurement Supported

Indicates whether current unbalance measurement or calculation is supported.

Motor Load Percentage Measurement Supported

Indicates that motor load is calculated and reported as a percentage of the applicable rated or configured motor load reference.

Motor Start Counter Supported

Indicates that the product counts cumulative motor starts.

Motor Start Permissive Output Supported

Indicates that the device can provide a permissive signal confirming that protection conditions allow the motor to start.

Motor Restart Permissive Calculation Supported

Indicates that the device evaluates thermal or protection conditions to determine whether a motor restart is currently permitted.

Motor Restart Time Remaining Reporting Supported

Indicates that the protection device reports the remaining restart-inhibit time before the motor may be started again.

Digital Input Count

Number of available digital inputs of the product.

Digital Output Count

Number of available digital outputs of the product.

Programmable Digital Inputs Supported

Indicates whether user-configurable functions can be assigned to one or more digital inputs.

Programmable Digital Outputs Supported

Indicates whether user-configurable functions can be assigned to one or more digital outputs.

Relay Output Count

Number of independent relay outputs or sets of switching contacts provided by the product.

Relay Output Contact Configuration

Contact configurations provided for the product relay outputs.

Relay Output Functions

Functions permanently assigned or assignable to the product relay outputs.

Analog Input Count

Number of integrated analogue input channels.

Analog Input Types

Analogue signal, sensor or resistance input types supported by the product.

Analog Output Count

Number of integrated analog outputs provided by the product.

Analog Output Types

Types of analog signals supported by the product outputs.

Local Configuration Supported

Indicates that device settings can be configured directly on the product using integrated controls or a local HMI.

Display of Measured Values Supported

Indicates that current measured values can be shown on the integrated display.

Display of Diagnostic Messages Supported

Indicates that fault, warning or diagnostic messages can be shown on the local display.

Display Status Color Indication Supported

Indicates that the display changes color or uses color coding to distinguish normal, warning, fault or configuration states.

Communication Supported

Indicates whether the product supports digital data exchange with external devices or systems.

Communication Protocols

List of supported digital data communication protocols.

Communication Interfaces

List of supported physical or logical digital communication interfaces.

Integrated Web Server

Indicates whether an integrated web server or web interface is provided for access to product functions.

Remote Configuration Supported

Indicates whether specified product settings can be read or changed remotely through a supported communication interface.

Remote Diagnostics Supported

Indicates whether diagnostic information, status data, or fault information can be obtained remotely.

Remote Measured Value Readout Supported

Indicates that current measured values can be read by an external controller, software system or communication master.

Diagnostics via Communication Supported

Indicates that warning, fault, status or diagnostic information can be transmitted through a supported digital communication interface.

Remote Reset Supported

Indicates whether a latched trip, fault, or alarm state can be reset remotely through a supported command or interface.

Remote Test Supported

Indicates that an internal test or test function can be initiated remotely through a supported interface.

Integrated Power Meter

Indicates whether the product includes integrated electrical measurement functionality beyond basic source-condition monitoring.

Voltage Measurement Supported

Indicates whether the product can measure and provide electrical voltage values.

Current Measurement Supported

Indicates whether the product can measure and provide electrical current values.

Frequency Measurement Supported

Indicates whether the product can measure and provide electrical network frequency values.

Power Measurement Supported

Indicates whether measurement of active, reactive, or apparent electrical power is supported.

Energy Measurement Supported

Indicates whether measurement or cumulative metering of electrical energy is supported.

Harmonics Measurement Supported

Indicates whether measurement or analysis of harmonic components of electrical quantities is supported.

Per-Phase Measurement Supported

Indicates that measured electrical quantities are available separately for individual phases.

Voltage Unbalance Measurement Supported

Indicates whether voltage unbalance measurement or calculation is supported.

Measurement Alarm Supported

Indicates that measured or calculated quantities can be compared with configured limits to generate alarms or status conditions.

Alarm Output Assignment Supported

Indicates that configured measurement alarms can be assigned to available relay, digital or equivalent outputs.

Event Log Supported

Indicates whether the product can store an internal event log.

Event Log Capacityevents

Maximum number of event records that can be stored in the product's internal log.

Real-Time Clock Present

Indicates whether an integrated real-time clock is provided for timekeeping, event time-stamping, or time-based functions.

Event Timestamp Supported

Indicates that stored events, warnings or faults can include a date and/or time stamp.

Trip History Supported

Indicates whether the product can store a history of protective trips or openings.

Trip History Capacitytrips

Maximum number of protective trip or opening records stored by the product.

Trip Measurements Recorded

Indicates whether measured electrical or other parameters associated with the moment of protective tripping are recorded.

Fault Waveform Capture Supported

Indicates whether electrical waveforms can be captured over an interval associated with a fault or protective trip.

Data Logger Supported

Indicates whether a data-logging function is provided for recording supported measurements, states, or process parameters.

Configurable Data Logger Trigger

Indicates whether the user can configure the condition that triggers or starts data logging.

Minimum / Maximum Measurement Supported

Indicates whether the product stores or provides minimum and maximum values of measured quantities.

Trend Data Supported

Indicates that measured-value trends or historical sequences can be stored, transmitted or evaluated.

Measured Value Memory Types

Types of measured values that can be retained by the product, such as last, minimum, maximum or fault-associated values.

Trip Counter Supported

Indicates whether the number of protective trips of the product is counted.

Operating Hours Counter Supported

Indicates whether accumulated product operating time or loaded operating time is counted according to the manufacturer's definition.

Self-Diagnostics Supported

Indicates whether the product performs internal diagnostic checks to detect or report internal faults.

Current Sensor Monitoring Supported

Indicates whether internal or external current sensors used by the protection system are monitored diagnostically.

Trip Circuit Monitoring Supported

Indicates whether the internal protection and trip circuit is monitored continuously or periodically.

Standards and Compliance21
Primary Product Standard

Primary normative document or standard according to which the manufacturer classifies or assesses the product.

Additional Standards

Additional normative documents and standards declared by the manufacturer as applicable to the product.

Declaration of Conformity Available

Indicates whether an official declaration of conformity is available for the product.

Certificate Available

Indicates whether a certificate relating to the declared certification or conformity of the product is available.

CE Marked

Indicates whether the CE marking is applied to the product where applicable.

UKCA Marked

Indicates whether the UKCA marking is applied to the product where applicable.

EAC Marked

Indicates whether the EAC marking is applied to the product where applicable.

UL Listed

Indicates whether the product has a declared UL Listed certification or recognition status.

UL Recognized

Indicates whether the product has a declared UL Recognized certification or recognition status.

cULus Marked

Indicates whether the cULus mark is applied to the product where applicable.

IEC 60529 Compliant

Indicates whether the manufacturer declares product compliance with IEC 60529.

IEC 62262 Compliant

Indicates whether the manufacturer declares product compliance with IEC 62262.

IEC 60068 Tested

Indicates whether the product has been tested according to applicable methods of the IEC 60068 series.

RoHS Compliant

Indicates whether product compliance with applicable RoHS restrictions on hazardous substances has been declared.

REACH Compliant

Indicates whether the manufacturer declares compliance of the product with applicable REACH Regulation requirements.

WEEE Applicable

Indicates whether the product falls within the scope of WEEE requirements for waste electrical and electronic equipment.

IEC 60255-1 Compliant

Compliance with applicable IEC 60255-1 common requirements for measuring relays and protection equipment.

IEC 60255-26 Compliant

Compliance with applicable IEC 60255-26 electromagnetic compatibility requirements for measuring relays and protection equipment.

IEC 60255-27 Compliant

Compliance with applicable IEC 60255-27 product safety requirements for measuring relays and protection equipment.

IEC 60947-4-1 Compliant

Compliance with IEC 60947-4-1 requirements applicable to electromechanical contactors and motor-starters.

UL 60947-4-1 Compliant

Compliance with UL 60947-4-1 requirements applicable to contactors and motor-starters.