TRASA3 Knowledge Base

Electrical Component Parameter Reference

An open technical reference for electrical component types, their applications, and selection parameters.

This material is also available in PL and RU.

Device description

Soft Starter

Semiconductor motor controller for limiting starting current and smoothly controlling voltage, torque, or current during starting and stopping.

A soft starter reduces electrical and mechanical stress during motor starting by controlled voltage variation and/or current limitation.

Depending on design, two or three phases may be controlled and algorithms may include voltage ramp, current limit, torque control, Kick Start, and different soft-stop modes.

Key parameters include initial-voltage range, current limit, start and stop ramp times, starts per hour, duty cycle, and thermal capability. After starting, the power semiconductors may be bypassed by an integrated or external bypass contactor.

Advanced versions may support bypass monitoring, diagnostics, different connection methods, and additional braking methods. Selection considers motor current and power, load characteristic, start duration and frequency, connection arrangement, and declared compliance with applicable IEC/EN/UL/CSA 60947-4-2 requirements.

Components in this subcategory

Semiconductor soft starters for induction motors and compatible motor loads, with integrated or external bypass.

Available parameters

Soft Starter

198 parameters
Dimensions4
Widthmm

External horizontal dimension of the product between its outermost lateral points.

Heightmm

External vertical dimension of the product from its lowest to its highest point.

Depthmm

External distance between the foremost and rearmost surfaces of the product.

Net Weightkg

Mass of the product itself, excluding transport packaging, additional accessories, and external equipment.

Materials and Finish7
Material

Primary material from which the product is manufactured.

Material Grade

Grade, alloy, class, or technical designation of the product's primary material.

Color

Primary visually perceived colour of the product's external surface.

RAL Color

Designation of the product's primary surface colour according to the RAL colour system.

Surface Finish

Type of final surface finish of the product determining its appearance and service properties.

Surface Treatment

Technological surface treatment applied to modify its protective, mechanical, or decorative properties.

Coating Type

Type of protective, functional, or decorative coating applied to the surface.

Mounting and Installation29
Mounting Type

Installation arrangement permitted by the product design, such as wall-mounted, flush-mounted, floor-mounted, or another specified mounting type.

Mounting Method

Method used to mechanically secure the product to a support, surface, or load-bearing structure.

Mounting Surface

Type of surface or supporting base to which the product may be fixed.

Orientation

Permissible spatial orientation of the component during installation and operation.

Number of Mounting Holes

Number of holes provided in the product for mechanical fixing.

Mounting Hole Diametermm

Diameter of the hole provided for a fixing element used when mounting the product.

Horizontal Mounting Hole Spacingmm

Distance between the centres of mounting holes in the horizontal direction.

Vertical Mounting Hole Spacingmm

Distance between the centres of mounting holes in the vertical direction.

Mounting Pattern Widthmm

Horizontal dimension of the mounting pattern between the outermost fixing points of the product.

Mounting Pattern Heightmm

Vertical dimension of the mounting pattern between the outermost fixing points of the product.

Mounting Screw Size

Size designation of the screw, bolt, or other threaded fastener used for mounting the product.

Mounting Thread

Designation of the thread provided in the product's mounting holes or fixing elements.

Mounting Tightening TorqueNm

Tightening torque recommended or permitted for fasteners during product installation.

Fasteners Included

Indicates whether the required fasteners are included with the product.

DIN Rail Mounting Supported

Indicates whether the design provides for mounting equipment on a DIN rail.

Direct Device Mounting Supported

Indicates whether equipment may be mounted directly to the mounting surface without an intermediate DIN rail.

Required Top Installation Clearancemm

Minimum free space required above the product for installation, cooling, or servicing.

Required Bottom Installation Clearancemm

Minimum free space required below the product for installation, cooling, or servicing.

Required Left Installation Clearancemm

Minimum free space required to the left of the product for installation or servicing.

Required Right Installation Clearancemm

Minimum free space required to the right of the product for installation or servicing.

Required Front Installation Clearancemm

Minimum free space required in front of the product for installation and normal operation.

Required Rear Installation Clearancemm

Minimum free space required behind the product for installation and normal operation.

Maximum Mounting Tilt Angle°

Maximum angle permitted by the manufacturer by which the product may deviate from the specified reference orientation during installation.

Minimum Ventilation Clearance Abovemm

Minimum unobstructed installation clearance required above the product for ventilation or heat dissipation.

Minimum Ventilation Clearance Belowmm

Minimum unobstructed installation clearance required below the product for ventilation or heat dissipation.

Minimum Ventilation Clearance Leftmm

Minimum unobstructed installation clearance required on the left side for normal cooling.

Minimum Ventilation Clearance Rightmm

Minimum unobstructed installation clearance required on the right side for normal cooling.

Minimum Ventilation Clearance Frontmm

Minimum unobstructed installation clearance required in front of the product for normal cooling.

Minimum Ventilation Clearance Rearmm

Minimum unobstructed installation clearance required behind the product for normal cooling.

Electrical Parameters58
Supply Current Type

Type of electrical current for which the product's main supply circuit is intended.

Rated VoltageV

Voltage value assigned to the product by the manufacturer for specified application conditions and characteristics.

Rated Operational VoltageV

Operating-circuit voltage with reference to which the product's performance characteristics are specified.

Minimum Operating VoltageV

Minimum voltage at which the manufacturer guarantees the intended operating mode of the product.

Maximum Operating VoltageV

Maximum voltage at which continuous operation of the product is permitted under the conditions declared by the manufacturer.

Rated FrequencyHz

AC frequency assigned to the product for normal operating conditions.

Minimum FrequencyHz

Lower limit of the electrical network or signal frequency at which product operation is permitted.

Maximum FrequencyHz

Upper limit of the electrical network or signal frequency at which product operation is permitted.

Rated CurrentA

Current assigned to the product by the manufacturer for the declared operating and thermal conditions.

Continuous Service CurrentA

Current that the product can carry continuously under the manufacturer's declared conditions without exceeding permissible temperature rise.

Rated Insulation VoltageV

Voltage with reference to which the product's insulation clearances and dielectric properties are specified.

Rated Impulse Withstand VoltagekV

Peak value of an impulse voltage of specified waveform that the product insulation must withstand without breakdown.

Dielectric Test VoltageV

Test voltage applied to verify the dielectric strength of the product insulation.

Minimum Insulation ResistanceMΩ

Minimum permissible insulation resistance between the specified electrically separated parts.

Overvoltage Category

Category characterizing the expected level of impulse overvoltages at the product's point of use.

Pollution Degree

Degree of pollution of the surrounding microenvironment considered when selecting insulation distances and product characteristics.

Electrical Protection Class

Class of protection against electric shock determined by the product design and protective connection method.

Supported Motor Types

Motor technologies and motor types that the product is designed to control, start, protect or drive.

Supported Motor Phase Configurations

Electrical phase configurations of motors supported by the product.

Supported Motor Winding Connections

Motor winding connection configurations supported by the product.

Minimum Supported Motor Rated VoltageV

Minimum motor rated voltage supported by the product.

Maximum Supported Motor Rated VoltageV

Maximum motor rated voltage supported by the product.

Minimum Supported Motor Rated CurrentA

Minimum motor rated current supported by the product.

Maximum Supported Motor Rated CurrentA

Maximum motor rated current supported by the product.

Minimum Supported Motor Rated PowerW

Minimum motor rated power supported by the product.

Maximum Supported Motor Rated PowerW

Maximum motor rated power supported by the product.

Minimum Supported Motor Rated FrequencyHz

Minimum motor rated frequency supported by the product.

Maximum Supported Motor Rated FrequencyHz

Maximum motor rated frequency supported by the product.

Minimum Supported Motor Rated Speedrpm

Minimum motor rated rotational speed supported by the product.

Maximum Supported Motor Rated Speedrpm

Maximum motor rated rotational speed supported by the product.

Minimum Supported Motor Pole Count

Minimum number of motor poles supported by the product.

Maximum Supported Motor Pole Count

Maximum number of motor poles supported by the product.

Minimum Supported Motor Service Factor

Minimum motor service factor supported or configurable for motor protection or control.

Maximum Supported Motor Service Factor

Maximum motor service factor supported or configurable for motor protection or control.

Supported Motor Starting Methods

Motor starting methods that the product can provide or manage.

Supported Motor Stop and Braking Methods

Motor stopping and braking methods supported by the product, including coast stop, controlled deceleration and electrical, regenerative or mechanical braking methods.

Supported Motor Rotation Directions

Motor rotation directions that the product can control.

Rated Motor PowerW

Manufacturer-declared motor power associated with the stated operational voltage and utilization category. UI may display the value in kW.

Rated Motor Power Reference VoltageV

Operational voltage associated with the stored rated motor power.

Rated Motor Power Utilization Category

Utilization category to which the stored rated motor power applies.

Main Terminal Connection Type

Conductor connection technology used specifically for the main power terminals of the switching device.

Minimum Main Terminal Conductor Cross-Sectionmm²

Minimum conductor cross-section accepted by the main power terminal.

Maximum Main Terminal Conductor Cross-Sectionmm²

Maximum conductor cross-section accepted by the main power terminal.

Main Terminal Tightening TorqueNm

Manufacturer-declared tightening torque specifically for screw, bolt or clamp-type main power terminals.

Control Terminal Connection Type

Conductor connection technology used specifically for the control-circuit terminals.

Minimum Control Terminal Conductor Cross-Sectionmm²

Minimum conductor cross-section accepted by the control-circuit terminal.

Maximum Control Terminal Conductor Cross-Sectionmm²

Maximum conductor cross-section accepted by the control-circuit terminal.

Control Terminal Tightening TorqueNm

Manufacturer-declared tightening torque specifically for a screw-type control-circuit terminal.

Soft Starter Controlled Phase Count

Number of motor supply phases in which the soft starter actively controls voltage using its semiconductor power stage.

Supported Soft Starter Line Connection Modes

Motor-circuit connection arrangements supported by the soft starter, such as in-line and inside-delta connection.

Soft Starter Initial Voltage Adjustable

Indicates that the initial motor voltage at the beginning of the starting ramp can be adjusted.

Minimum Soft Starter Initial Voltage%

Minimum configurable initial motor voltage expressed as a percentage of the applicable line or rated motor voltage.

Maximum Soft Starter Initial Voltage%

Maximum configurable initial motor voltage expressed as a percentage of the applicable line or rated motor voltage.

Soft Starter Rated Starting Current Ratio%

Manufacturer-declared starting current associated with the rated soft-starter starting duty, expressed as a percentage of the applicable rated motor or starter current.

Soft Starter Rated Start Times

Manufacturer-declared maximum or reference motor starting duration associated with the stated starting-duty rating.

Minimum Time Between Soft Starter Startss

Minimum required interval between consecutive motor starts under the manufacturer-declared duty conditions.

On-Load Factor%

Manufacturer-declared proportion of the complete operating cycle during which the product carries load current under the stated duty or utilization rating.

Maximum Starts per Hour

Maximum permitted or configurable number of motor starts within one hour.

Protection and Safety13
IP Rating

Degree of enclosure protection against access to hazardous parts and ingress of solid objects and water, designated by the IP code.

Front-Side IP Rating

IP degree of protection provided by the accessible front side of the product after its intended installation.

IK Rating

Class of enclosure resistance to external mechanical impacts designated by the IK code.

Ingress Protection Certified

Indicates whether the declared ingress protection of the enclosure has been verified by certification or testing.

Protection Against Direct Contact

Method or level of protection of the user against direct contact with hazardous live parts.

Protection Functions

Set of protection functions integrated into the product or provided by it in its normal intended configuration.

Supported Reset Modes

Reset or restart modes supported after the condition that caused a trip, protection action, alarm or safety stop has been cleared.

Trip Indicator Present

Indicates whether a local mechanical or electronic indicator shows that the circuit breaker has tripped protectively.

Short-Circuit Current RatingkA

Manufacturer-declared permissible short-circuit current value for the product or assembly under specified conditions.

Short-Circuit Rating Conditions

Conditions associated with the declared short-circuit withstand rating or SCCR, including required type, class, rating, or other restrictions of the upstream protective device.

Soft Starter Motor Current Limit Adjustable

Indicates that motor starting current can be limited to a configurable multiple or percentage of the motor current reference.

Minimum Soft Starter Motor Current Limit%

Minimum configurable motor current limit expressed as a percentage of the applicable motor full-load or rated-current reference.

Maximum Soft Starter Motor Current Limit%

Maximum configurable motor current limit expressed as a percentage of the applicable motor full-load or rated-current reference.

Environmental Conditions27
Minimum Operating Temperature°C

Minimum ambient temperature at which normal operation of the product is permitted.

Maximum Operating Temperature°C

Maximum ambient temperature at which normal operation of the product is permitted.

Minimum Storage Temperature°C

Minimum ambient temperature permitted during storage of the product while not in operation.

Maximum Storage Temperature°C

Maximum ambient temperature permitted during storage of the product while not in operation.

Minimum Relative Humidity%

Minimum relative air humidity permitted for the declared operating or test condition.

Maximum Relative Humidity%

Maximum relative air humidity permitted for the declared operating or test condition.

Relative Humidity Reference Temperature°C

Temperature at which the corresponding relative humidity value is specified or standardized.

Humidity Condition

Nature of the humidity conditions for which product operation or resistance is declared.

Non-Condensing Humidity

Indicates whether the permissible humidity value applies only to non-condensing conditions.

Maximum Installation Altitudem

Maximum altitude above sea level at which the product may be installed without exceeding the declared conditions.

Altitude Derating Required

Indicates whether the permissible product load must be reduced as installation altitude increases.

Altitude Derating Startm

Altitude above sea level above which the permissible product load must be reduced.

Vibration Resistant

Indicates whether the product's resistance to vibration has been verified under the declared conditions.

Minimum Vibration FrequencyHz

Lower limit of vibration frequency applied or permitted in the relevant test.

Maximum Vibration FrequencyHz

Upper limit of vibration frequency applied or permitted in the relevant test.

Vibration Accelerationm/s²

Amplitude or test-method-specified acceleration of vibration applied during product testing.

Mechanical Shock Resistant

Indicates whether the product's resistance to short-duration mechanical shocks has been verified.

Shock Accelerationm/s²

Maximum acceleration generated during mechanical shock testing of the product.

Shock Durationms

Duration of an individual mechanical shock pulse during product testing.

Cooling Method

Primary cooling method used by the product during normal operation.

Maximum Acoustic Noise LeveldB(A)

Maximum manufacturer-declared acoustic noise level under the specified operating and measurement conditions.

Cooling Airflow Direction

Principal airflow direction through or around the product for normal manufacturer-declared cooling.

Temperature Derating Rate%/K

Percentage reduction of usable output capability per kelvin above the manufacturer-declared derating threshold.

Altitude Derating Rate%/1000m

Percentage reduction of usable output capability per 1000 metres above the manufacturer-declared derating altitude.

PCB Conformal Coating Present

Indicates that one or more internal printed circuit boards are protected by a conformal coating.

PCB Conformal Coating Type

Principal conformal coating material applied to internal printed circuit boards.

Tropicalization Treatment

Indicates that the product incorporates manufacturer-declared measures intended for operation in hot and humid tropical environments.

Included Equipment2
Integrated Soft Starter Bypass Contactor Present

Indicates that the soft starter incorporates an internal bypass contactor that carries motor current after starting.

External Soft Starter Bypass Contactor Supported

Indicates that the manufacturer supports operation with an external bypass contactor.

Special Features38
Digital Input Count

Number of available digital inputs of the product.

Digital Output Count

Number of available digital outputs of the product.

Programmable Digital Inputs Supported

Indicates whether user-configurable functions can be assigned to one or more digital inputs.

Programmable Digital Outputs Supported

Indicates whether user-configurable functions can be assigned to one or more digital outputs.

Relay Output Count

Number of independent relay outputs or sets of switching contacts provided by the product.

Relay Output Contact Configuration

Contact configurations provided for the product relay outputs.

Relay Output Functions

Functions permanently assigned or assignable to the product relay outputs.

Analog Input Count

Number of integrated analogue input channels.

Analog Input Types

Analogue signal, sensor or resistance input types supported by the product.

Analog Output Count

Number of integrated analog outputs provided by the product.

Analog Output Types

Types of analog signals supported by the product outputs.

Communication Supported

Indicates whether the product supports digital data exchange with external devices or systems.

Communication Protocols

List of supported digital data communication protocols.

Communication Interfaces

List of supported physical or logical digital communication interfaces.

Event Log Supported

Indicates whether the product can store an internal event log.

Event Log Capacityevents

Maximum number of event records that can be stored in the product's internal log.

Operating Hours Counter Supported

Indicates whether accumulated product operating time or loaded operating time is counted according to the manufacturer's definition.

Trip Counter Supported

Indicates whether the number of protective trips of the product is counted.

Self-Diagnostics Supported

Indicates whether the product performs internal diagnostic checks to detect or report internal faults.

Soft Starter Start Control Modes

Control algorithms supported during motor acceleration and starting.

Soft Starter Stop Control Modes

Controlled motor stopping methods supported by the soft starter.

Soft Starter Start Ramp Time Adjustable

Indicates that the acceleration or starting ramp duration can be adjusted.

Minimum Soft Starter Start Ramp Times

Minimum configurable starting ramp duration.

Maximum Soft Starter Start Ramp Times

Maximum configurable starting ramp duration.

Soft Starter Stop Ramp Time Adjustable

Indicates that the controlled deceleration or soft-stop ramp duration can be adjusted.

Minimum Soft Starter Stop Ramp Times

Minimum configurable controlled stopping ramp duration.

Maximum Soft Starter Stop Ramp Times

Maximum configurable controlled stopping ramp duration.

Soft Starter Initial Torque Adjustable

Indicates that an initial motor starting-torque reference can be adjusted.

Minimum Soft Starter Initial Torque%

Minimum configurable initial torque reference expressed as a percentage of the applicable motor torque reference.

Maximum Soft Starter Initial Torque%

Maximum configurable initial torque reference expressed as a percentage of the applicable motor torque reference.

Soft Starter Kick Start Supported

Indicates support for a short elevated starting command used to overcome high static friction or difficult initial load breakaway.

Minimum Soft Starter Kick Start Level%

Minimum configurable kick-start voltage, torque or manufacturer-defined starting level expressed as a percentage of its applicable reference.

Maximum Soft Starter Kick Start Level%

Maximum configurable kick-start voltage, torque or manufacturer-defined starting level expressed as a percentage of its applicable reference.

Minimum Soft Starter Kick Start Durations

Minimum configurable kick-start duration.

Maximum Soft Starter Kick Start Durations

Maximum configurable kick-start duration.

Automatic Soft Starter Bypass Transition

Indicates that transfer between semiconductor control and bypass operation occurs automatically.

Soft Starter Bypass Feedback Supported

Indicates that bypass-contactor state can be monitored or verified by the soft starter.

Soft Starter Bypass Control Output Present

Indicates that a dedicated output is provided for controlling an external bypass contactor.

Standards and Compliance20
Primary Product Standard

Primary normative document or standard according to which the manufacturer classifies or assesses the product.

Additional Standards

Additional normative documents and standards declared by the manufacturer as applicable to the product.

Declaration of Conformity Available

Indicates whether an official declaration of conformity is available for the product.

Certificate Available

Indicates whether a certificate relating to the declared certification or conformity of the product is available.

CE Marked

Indicates whether the CE marking is applied to the product where applicable.

UKCA Marked

Indicates whether the UKCA marking is applied to the product where applicable.

EAC Marked

Indicates whether the EAC marking is applied to the product where applicable.

UL Listed

Indicates whether the product has a declared UL Listed certification or recognition status.

UL Recognized

Indicates whether the product has a declared UL Recognized certification or recognition status.

cULus Marked

Indicates whether the cULus mark is applied to the product where applicable.

IEC 60529 Compliant

Indicates whether the manufacturer declares product compliance with IEC 60529.

IEC 62262 Compliant

Indicates whether the manufacturer declares product compliance with IEC 62262.

IEC 60068 Tested

Indicates whether the product has been tested according to applicable methods of the IEC 60068 series.

RoHS Compliant

Indicates whether product compliance with applicable RoHS restrictions on hazardous substances has been declared.

REACH Compliant

Indicates whether the manufacturer declares compliance of the product with applicable REACH Regulation requirements.

WEEE Applicable

Indicates whether the product falls within the scope of WEEE requirements for waste electrical and electronic equipment.

IEC 60947-4-2 Compliant

Compliance with IEC 60947-4-2 requirements applicable to semiconductor motor controllers, starters and soft-starters.

EN IEC 60947-4-2 Compliant

Compliance with the European adoption EN IEC 60947-4-2 applicable to semiconductor motor controllers, starters and soft-starters.

UL 60947-4-2 Compliant

Compliance with UL 60947-4-2 requirements applicable to AC semiconductor motor controllers and starters.

CSA C22.2 No. 60947-4-2 Compliant

Compliance with CSA C22.2 No. 60947-4-2 requirements applicable to semiconductor motor controllers and starters.