Electrical Component Parameter Reference

An open technical reference for electrical component types, their applications, and selection parameters.

This material is also available in PL and RU.

Device description

Energy Management System

System coordinating generation, storage, grid exchange, and controllable loads to optimize site energy flows.

An energy management system coordinates PV, batteries, inverters, EVSE, meters, and controllable loads. It receives measurements and forecasts, generates setpoints, and optimizes site operation for cost, power, self-consumption, or energy reserve.

Functions may include self-consumption optimization, peak shaving, import/export limiting, load prioritization, and battery reserve SoC control. Advanced systems use time-of-use and dynamic tariffs, day-ahead prices, PV-generation forecasts, load forecasts, and weather data for scheduled dispatch.

For resilient operation, communication-loss fallback strategies, local optimization, safe default policy, and asset-availability monitoring are important. An EMS may operate locally, in the cloud, or in a hybrid architecture and may integrate external meters and remote setpoints.

Selection considers number and types of controlled assets, response time, forecasting horizon, tariff functions, offline operation, and integration interfaces.

Components in this subcategory

This subcategory includes local and cloud-based EMS solutions for PV, ESS, EV charging, grid interaction, and controllable loads.

Available parameters

Energy Management System

321 parameters
General6
Product Series

Commercial or technical designation of a manufacturer's product family sharing a common design and compatible characteristics.

Application

Range of tasks and systems for which the manufacturer recommends the component.

Intended Use

Primary function of the device and its intended use as defined by its design and the manufacturer's documentation.

Installation Location

Permissible installation location of the product: indoors, outdoors, in a technical area, or as part of equipment.

Installation Environment

Environmental conditions under which installation and operation of the product are permitted.

Orientation

Permissible spatial orientation of the component during installation and operation.

Dimensions3
Widthmm

External horizontal dimension of the product between its outermost lateral points.

Heightmm

External vertical dimension of the product from its lowest to its highest point.

Depthmm

External distance between the foremost and rearmost surfaces of the product.

Capacity and Layout15
Digital Input Count

Number of available digital inputs of the product.

Digital Output Count

Number of available digital outputs of the product.

Relay Output Count

Number of independent relay outputs or sets of switching contacts provided by the product.

Analog Output Count

Number of integrated analog outputs provided by the product.

Analog Input Count

Number of integrated analogue input channels.

Monitoring Threshold Count

Number of independently usable monitoring, switching or alarm thresholds provided by the device.

Maximum Load Priority Level Count

Maximum number of independently configurable load-priority levels.

Maximum Controllable Asset Count

Maximum number of independently addressable energy assets that can participate in EMS control.

Maximum External Energy Meter Count

Maximum number of external electricity meters that can be simultaneously integrated into the EMS.

Event Log Capacityevents

Maximum number of event records that can be stored in the product's internal log.

Ethernet Port Count

Number of integrated physical Ethernet communication ports.

RS-485 Port Count

Number of integrated physical RS-485 communication interfaces.

USB Port Count

Number of integrated physical USB ports provided by the product, including charging, data, communication or programming ports.

CAN Port Count

Number of integrated physical CAN communication interfaces.

Configurable Serial Combo Port Count

Number of physical serial ports that can be configured for more than one electrical serial standard.

Materials and Finish8
Color

Primary visually perceived colour of the product's external surface.

RAL Color

Designation of the product's primary surface colour according to the RAL colour system.

Surface Finish

Type of final surface finish of the product determining its appearance and service properties.

Surface Treatment

Technological surface treatment applied to modify its protective, mechanical, or decorative properties.

Coating Type

Type of protective, functional, or decorative coating applied to the surface.

Coating Material

Material or chemical basis of the coating applied to the surface of the product or one of its parts.

Material

Primary material from which the product is manufactured.

Material Grade

Grade, alloy, class, or technical designation of the product's primary material.

Mounting and Installation17
DIN Rail Type

Profile type of the DIN rail installed in the product or specified for compatible mounting.

Mounting Type

Installation arrangement permitted by the product design, such as wall-mounted, flush-mounted, floor-mounted, or another specified mounting type.

Mounting Method

Method used to mechanically secure the product to a support, surface, or load-bearing structure.

Mounting Surface

Type of surface or supporting base to which the product may be fixed.

Number of Mounting Holes

Number of holes provided in the product for mechanical fixing.

Mounting Hole Diametermm

Diameter of the hole provided for a fixing element used when mounting the product.

Mounting Hole Shape

Geometric shape of the hole intended for mechanical fixing of the product.

Horizontal Mounting Hole Spacingmm

Distance between the centres of mounting holes in the horizontal direction.

Vertical Mounting Hole Spacingmm

Distance between the centres of mounting holes in the vertical direction.

Mounting Pattern Widthmm

Horizontal dimension of the mounting pattern between the outermost fixing points of the product.

Mounting Pattern Heightmm

Vertical dimension of the mounting pattern between the outermost fixing points of the product.

Mounting Screw Size

Size designation of the screw, bolt, or other threaded fastener used for mounting the product.

Mounting Thread

Designation of the thread provided in the product's mounting holes or fixing elements.

Mounting Tightening TorqueNm

Tightening torque recommended or permitted for fasteners during product installation.

Fasteners Included

Indicates whether the required fasteners are included with the product.

DIN Rail Mounting Supported

Indicates whether the design provides for mounting equipment on a DIN rail.

Direct Device Mounting Supported

Indicates whether equipment may be mounted directly to the mounting surface without an intermediate DIN rail.

Electrical Parameters84
Number of Phases

Number of phases of the electrical system for which the product is designed to be connected or used.

Voltage Measurement Supported

Indicates whether the product can measure and provide electrical voltage values.

Current Measurement Supported

Indicates whether the product can measure and provide electrical current values.

Frequency Measurement Supported

Indicates whether the product can measure and provide electrical network frequency values.

Power Measurement Supported

Indicates whether measurement of active, reactive, or apparent electrical power is supported.

Energy Measurement Supported

Indicates whether measurement or cumulative metering of electrical energy is supported.

Measurement Principle

Electrical measurement principle used for evaluation of the monitored signal, such as true RMS, RMS, average-value or direct-value measurement.

Minimum Measurement FrequencyHz

Minimum signal frequency accepted by the measuring circuit for the declared monitoring or measurement function.

Maximum Measurement FrequencyHz

Maximum signal frequency accepted by the measuring circuit for the declared monitoring or measurement function.

Voltage Measurement Accuracy%

Manufacturer-declared accuracy of voltage measurement where expressed as a single percentage value.

Minimum Voltage Measurement RangeV

Lowest voltage that can be measured or monitored within the manufacturer-declared measuring range.

Maximum Voltage Measurement RangeV

Highest voltage that can be measured or monitored within the manufacturer-declared measuring range.

Frequency Measurement AccuracyHz

Manufacturer-declared absolute accuracy of frequency measurement.

Minimum Current Measurement RangeA

Lowest current that can be measured or monitored within the manufacturer-declared measuring range.

Maximum Current Measurement RangeA

Highest current that can be measured or monitored within the manufacturer-declared measuring range.

Current Transformer Input Supported

Indicates that the measuring circuit supports connection through an external current transformer.

Configurable Current Transformer Ratio

Indicates that the current transformer ratio used for measurement scaling can be configured in the device.

Minimum Current Transformer Primary Current SettingA

Minimum configurable primary current value used for current transformer scaling.

Maximum Current Transformer Primary Current SettingA

Maximum configurable primary current value used for current transformer scaling.

Supported Current Transformer Secondary Currents

Standard secondary current ratings of external current transformers supported by the measuring input.

Active Power Measurement Supported

Indicates that active electrical power is measured or calculated by the device.

Current Measurement Accuracy%

Manufacturer-declared relative accuracy of current measurement where expressed as a percentage.

Reactive Power Measurement Supported

Indicates that reactive electrical power is measured or calculated by the device.

Apparent Power Measurement Supported

Indicates that apparent electrical power is measured or calculated by the device.

Power Factor Measurement Supported

Indicates that the electrical power factor is measured or calculated by the device.

Current Measurement Connection Method

Supported methods for connecting the monitored current to the measuring device.

Power Flow Direction Detection Supported

Indicates that the device can distinguish the direction of active power flow.

Supported Power Flow Directions

Power-flow directions that can be measured or evaluated by the product.

Minimum Active Power MeasurementW

Lower limit of the manufacturer-declared active-power measuring range.

Maximum Active Power MeasurementW

Upper limit of the manufacturer-declared active-power measuring range.

Active Power Measurement Accuracy%

Manufacturer-declared relative accuracy of active-power measurement.

Minimum Reactive Power Measurementvar

Lower limit of the manufacturer-declared reactive-power measuring range.

Maximum Reactive Power Measurementvar

Upper limit of the manufacturer-declared reactive-power measuring range.

Reactive Power Measurement Accuracy%

Manufacturer-declared relative accuracy of reactive-power measurement.

Minimum Apparent Power MeasurementVA

Lower limit of the manufacturer-declared apparent-power measuring range.

Maximum Apparent Power MeasurementVA

Upper limit of the manufacturer-declared apparent-power measuring range.

Apparent Power Measurement Accuracy%

Manufacturer-declared relative accuracy of apparent-power measurement.

Minimum Power Factor Measurement

Lower limit of the manufacturer-declared power-factor measuring range.

Maximum Power Factor Measurement

Upper limit of the manufacturer-declared power-factor measuring range.

Power Factor Measurement Accuracy

Manufacturer-declared absolute accuracy of power-factor measurement expressed as a cos φ value difference.

Inductive / Capacitive Power Factor Discrimination Supported

Indicates that the device distinguishes inductive lagging and capacitive leading power-factor conditions.

Metering Connection Type

Overall electrical measurement connection topology of the device, distinguishing direct measurement and operation through external current, voltage, shunt, Rogowski or sensor interfaces.

Voltage Measurement Connection Method

Supported methods for connecting the voltage measuring circuit, such as direct connection or connection through an external voltage transformer.

Voltage Transformer Input Supported

Indicates that the measuring device supports voltage measurement through an external voltage transformer.

Configurable Voltage Transformer Ratio

Indicates that the voltage transformer ratio used for measurement scaling can be configured in the device.

Minimum Voltage Transformer Primary Voltage SettingV

Minimum configurable primary voltage value used for voltage-transformer measurement scaling.

Maximum Voltage Transformer Primary Voltage SettingV

Maximum configurable primary voltage value used for voltage-transformer measurement scaling.

Supported Voltage Transformer Secondary Voltages

Standard secondary voltage ratings of external voltage transformers supported by the measuring input.

Bidirectional Energy Measurement Supported

Indicates separate measurement or registration of energy flowing in both import and export directions.

Four-Quadrant Measurement Supported

Indicates support for four-quadrant measurement of active and reactive power or energy, distinguishing direction and reactive quadrant where applicable.

Per-Phase Measurement Supported

Indicates that measured electrical quantities are available separately for individual phases.

Neutral Current Measurement Supported

Indicates that current in the neutral conductor can be measured independently.

Total System Measurement Supported

Indicates that aggregate or total system values are calculated in addition to individual phase measurements.

Active Energy Measurement Supported

Indicates that the device measures or accumulates active electrical energy.

Reactive Energy Measurement Supported

Indicates that the device measures or accumulates reactive electrical energy.

Apparent Energy Measurement Supported

Indicates that the device measures or accumulates apparent electrical energy.

Imported Energy Measurement Supported

Indicates separate measurement or accumulation of imported energy.

Exported Energy Measurement Supported

Indicates separate measurement or accumulation of exported energy.

Net Energy Measurement Supported

Indicates calculation or accumulation of net energy resulting from import and export energy flow.

Supported Reactive Energy Quadrants

Reactive-energy quadrants that can be separately measured or registered.

Minimum Grid Import Power LimitW

Minimum configurable site grid-import active-power limit.

Maximum Grid Import Power LimitW

Maximum configurable site grid-import active-power limit.

Minimum Grid Export Power LimitW

Minimum configurable active-power export limit applied at the site grid connection point.

Maximum Grid Export Power LimitW

Maximum configurable active-power export limit applied at the site grid connection point.

Minimum Reserve SoC Setting%

Minimum configurable battery state-of-charge reserve setpoint.

Maximum Reserve SoC Setting%

Maximum configurable battery state-of-charge reserve setpoint.

Site Power Control Response Timems

Manufacturer-declared response time between a valid site power-control request and initiation of the corresponding EMS control action.

Supply Current Type

Type of electrical current for which the product's main supply circuit is intended.

Rated VoltageV

Voltage value assigned to the product by the manufacturer for specified application conditions and characteristics.

Rated AC VoltageV

Rated RMS value of alternating voltage assigned to the product by the manufacturer.

Rated DC VoltageV

Rated direct voltage assigned to the product by the manufacturer.

Maximum Operating VoltageV

Maximum voltage at which continuous operation of the product is permitted under the conditions declared by the manufacturer.

Minimum Operating VoltageV

Minimum voltage at which the manufacturer guarantees the intended operating mode of the product.

Rated FrequencyHz

AC frequency assigned to the product for normal operating conditions.

Conductor Connection Type

Conductor connection methods supported by the specified terminals or connection elements.

Terminal Tightening TorqueNm

Tightening torque specified by the manufacturer for a screw or bolted terminal connection.

Rated Insulation VoltageV

Voltage with reference to which the product's insulation clearances and dielectric properties are specified.

Rated Impulse Withstand VoltagekV

Peak value of an impulse voltage of specified waveform that the product insulation must withstand without breakdown.

Dielectric Test VoltageV

Test voltage applied to verify the dielectric strength of the product insulation.

Minimum Insulation ResistanceMΩ

Minimum permissible insulation resistance between the specified electrically separated parts.

Overvoltage Category

Category characterizing the expected level of impulse overvoltages at the product's point of use.

Pollution Degree

Degree of pollution of the surrounding microenvironment considered when selecting insulation distances and product characteristics.

Insulation Type

Type of electrical insulation used, considered in terms of its protective function and construction.

Electrical Protection Class

Class of protection against electric shock determined by the product design and protective connection method.

Protection and Safety25
Energy Management Behavior on Communication Loss

Energy-management control behavior applied when communication with controlled assets, supervisory systems or required external services is lost.

Energy Management Communication Loss Timeouts

Manufacturer-declared communication-loss duration after which the EMS applies its configured communication-failure behavior.

Automatic Local Fallback Supported

Indicates that the EMS can automatically transition from remote, cloud or supervisory control to locally executed control after loss of the external control path.

Energy Management Fallback Strategy

Primary control strategy used by the EMS after loss of the normal supervisory, cloud or external optimization source.

Last Valid Dispatch Hold Times

Maximum time for which the last valid energy-dispatch or power-control setpoint may remain active after loss of its command source.

Safe Default Energy Policy Supported

Indicates that a predefined safe energy-management policy can be applied when normal optimization or supervisory control is unavailable.

Cloud Connection Loss Alarm Supported

Indicates that loss of a required or configured cloud connection can generate an explicit EMS alarm or diagnostic event.

Halogen-Free

Indicates whether the product material is classified as halogen-free according to the characteristics declared by the manufacturer.

IP Rating

Degree of enclosure protection against access to hazardous parts and ingress of solid objects and water, designated by the IP code.

IK Rating

Class of enclosure resistance to external mechanical impacts designated by the IK code.

Impact EnergyJ

Mechanical impact energy that the product or enclosure can withstand in the specified test.

NEMA Enclosure Rating

Enclosure type or rating under the NEMA system characterizing the conditions and types of external influences against which protection is provided.

Ingress Protection Certified

Indicates whether the declared ingress protection of the enclosure has been verified by certification or testing.

Protection Against Direct Contact

Method or level of protection of the user against direct contact with hazardous live parts.

Finger-Safe

Indicates whether the design prevents finger access to hazardous live parts in the intended condition.

Touch-Safe

Indicates whether the design provides protection against accidental contact with hazardous live parts.

Flammability Class

Classification of a material according to its ability to ignite, sustain combustion, and cease burning under a specified test.

Glow-Wire Test Temperature°C

Temperature of the heated wire used when testing the material or product against an ignition source.

User Authentication Supported

Indicates that access to network, web, API or remote configuration functions can require authenticated user credentials.

Encrypted Communication Supported

Indicates support for encrypted data communication through one or more manufacturer-supported communication services.

Supported TLS Versions

Transport Layer Security protocol versions supported for protected network communication.

Role-Based Access Control Supported

Indicates that user permissions can be differentiated by user role or authorization level.

Security Event Logging Supported

Indicates that security-relevant events such as authentication failures or configuration access can be recorded.

Secure Boot Supported

Indicates that the device verifies the integrity or authenticity of executable firmware during startup.

Signed Firmware Update Supported

Indicates that firmware update packages are cryptographically authenticated before installation.

Environmental Conditions21
Minimum Operating Temperature°C

Minimum ambient temperature at which normal operation of the product is permitted.

Maximum Operating Temperature°C

Maximum ambient temperature at which normal operation of the product is permitted.

Maximum 24-Hour Average Temperature°C

Maximum permissible average ambient temperature over a consecutive 24-hour period.

Minimum Storage Temperature°C

Minimum ambient temperature permitted during storage of the product while not in operation.

Maximum Storage Temperature°C

Maximum ambient temperature permitted during storage of the product while not in operation.

Minimum Transport Temperature°C

Minimum ambient temperature permitted during transportation of the product.

Maximum Transport Temperature°C

Maximum ambient temperature permitted during transportation of the product.

Minimum Installation Temperature°C

Minimum ambient temperature at which the manufacturer permits installation of the product.

Maximum Installation Temperature°C

Maximum ambient temperature at which the manufacturer permits installation of the product.

Temperature Derating Required

Indicates whether permissible electrical or thermal loading must be reduced as temperature changes.

Temperature Derating Start°C

Temperature above which the permissible product load must be reduced.

Temperature Derating Curve Available

Indicates whether the manufacturer has published the relationship between permissible product load and temperature.

Minimum Relative Humidity%

Minimum relative air humidity permitted for the declared operating or test condition.

Maximum Relative Humidity%

Maximum relative air humidity permitted for the declared operating or test condition.

Non-Condensing Humidity

Indicates whether the permissible humidity value applies only to non-condensing conditions.

Maximum Installation Altitudem

Maximum altitude above sea level at which the product may be installed without exceeding the declared conditions.

Minimum Installation Altitudem

Minimum altitude relative to sea level for which the manufacturer specifies permissible installation conditions.

Altitude Derating Required

Indicates whether the permissible product load must be reduced as installation altitude increases.

Altitude Derating Startm

Altitude above sea level above which the permissible product load must be reduced.

Vibration Resistant

Indicates whether the product's resistance to vibration has been verified under the declared conditions.

Mechanical Shock Resistant

Indicates whether the product's resistance to short-duration mechanical shocks has been verified.

Included Equipment6
Documentation Included

Indicates whether documentation is included in the product's standard supply.

Local HMI Present

Indicates whether a local human-machine interface (HMI) is provided for monitoring, configuration, or control.

Display Present

Indicates whether the product has an integrated local display.

Display Type

Technology or construction type of the product's integrated display.

Display Backlight

Indicates whether the integrated display has a backlight.

Real-Time Clock Present

Indicates whether an integrated real-time clock is provided for timekeeping, event time-stamping, or time-based functions.

Special Features103
Minimum / Maximum Measurement Supported

Indicates whether the product stores or provides minimum and maximum values of measured quantities.

Demand Measurement Supported

Indicates whether demand calculation or measurement is supported for specified electrical quantities.

Programmable Digital Inputs Supported

Indicates whether user-configurable functions can be assigned to one or more digital inputs.

Programmable Digital Outputs Supported

Indicates whether user-configurable functions can be assigned to one or more digital outputs.

Monitoring Functions

Electrical or physical monitoring functions provided by the device, such as overvalue, undervalue, window, phase, frequency, current, power, insulation, temperature or level monitoring.

Multi-Tariff Metering Supported

Indicates that energy values can be accumulated separately in multiple tariff registers.

Tariff Count

Maximum number of independent energy tariffs supported by the meter.

Tariff Switching Methods

Methods supported for selecting or switching active tariff registers.

Total Energy Register Supported

Indicates the presence of a cumulative total-energy register.

Partial Energy Register Supported

Indicates the presence of one or more partial or subtotal energy registers.

Partial Energy Register Resettable

Indicates that a partial energy register can be reset without clearing the legally relevant total-energy register.

Maximum Demand Register Supported

Indicates storage of the maximum calculated demand value.

Configurable Demand Interval

Indicates that the demand calculation interval can be configured.

Minimum Demand Intervals

Minimum configurable interval used for demand calculation.

Maximum Demand Intervals

Maximum configurable interval used for demand calculation.

Load Profile Supported

Indicates that time-series load or energy profile data can be recorded internally.

Minimum Load Profile Intervals

Minimum configurable interval between stored load-profile records.

Maximum Load Profile Intervals

Maximum configurable interval between stored load-profile records.

Load Profile Capacityrecords

Maximum number of load-profile records retained internally.

Measurement Data Logging Supported

Indicates that measured electrical values can be stored internally as historical measurement records.

Measurement Data Log Capacityrecords

Maximum number of historical measurement records retained internally.

Configurable Measurement Logging Interval

Indicates that the interval between periodic measurement records can be configured.

Minimum Measurement Logging Intervals

Minimum configurable interval between periodically stored measurement records.

Maximum Measurement Logging Intervals

Maximum configurable interval between periodically stored measurement records.

Historical Data Export Supported

Indicates that stored measurement or event history can be exported from the device.

Maximum Demand Reset Supported

Indicates that the stored maximum demand register can be reset using a manufacturer-supported procedure.

Phase Sequence Indication Supported

Indicates that the detected phase sequence or phase rotation direction can be presented locally or through communication.

Demand Quantities

Electrical quantities for which interval demand can be calculated or registered.

Demand Calculation Methods

Demand calculation algorithms supported by the measuring device.

Demand Subinterval Supported

Indicates that a demand interval may be divided into shorter subintervals for rolling or sliding demand calculation.

Minimum Demand Subintervals

Minimum configurable demand-calculation subinterval.

Maximum Demand Subintervals

Maximum configurable demand-calculation subinterval.

Predicted Demand Supported

Indicates calculation of a projected demand value before completion of the current demand interval.

Measurement Alarm Supported

Indicates that measured or calculated quantities can be compared with configured limits to generate alarms or status conditions.

Alarm Output Assignment Supported

Indicates that configured measurement alarms can be assigned to available relay, digital or equivalent outputs.

Input Wiring Error Detection Supported

Indicates that the measuring device can detect manufacturer-defined wiring errors affecting its voltage or current measurement inputs.

CT Polarity Error Detection Supported

Indicates that incorrect current-transformer polarity or reversed current measurement direction can be detected.

Phase Assignment Error Detection Supported

Indicates that an incorrect relationship between voltage and current phase channels can be detected.

Measurement Overrange Indication Supported

Indicates explicit indication when an input or calculated measured quantity exceeds its valid measurement range.

Measurement Underrange Indication Supported

Indicates explicit indication when an input or measured quantity is below its valid or usable measurement range.

Energy Cost Calculation Supported

Indicates that measured energy consumption can be converted into an estimated monetary cost using user-configurable tariff information.

Integrated Power Meter

Indicates whether the product includes integrated electrical measurement functionality beyond basic source-condition monitoring.

Load Shedding Supported

Indicates whether shedding or limiting part of the load under specified power-system conditions is supported.

Manual Override Supported

Indicates whether local manual override is provided with intended priority over automatic, programmed, or electrically commanded operation.

Remote Operation Supported

Indicates whether the product's main operating function can be controlled by a remote command.

Export Power Limiting Supported

Indicates that active power exported to the utility grid can be limited.

Zero Export Supported

Indicates support for operation intended to prevent net active-power export to the utility grid.

External Export Meter Supported

Indicates that an external meter or power sensor can be used for grid export limitation or energy-flow control.

Self-Consumption Optimization Supported

Indicates that the energy management system can coordinate generation, storage and loads to increase local consumption of locally generated energy.

Peak Shaving Supported

Indicates that the EMS can reduce site power peaks using controllable generation, storage or loads.

Demand Limiting Supported

Indicates that the EMS can actively control site demand to remain below a configured demand limit.

Grid Import Power Limiting Supported

Indicates that the EMS can maintain utility-grid import below a configured active-power limit.

Load Prioritization Supported

Indicates that controllable loads can be assigned priorities for energy-management decisions.

Battery Reserve SoC Control Supported

Indicates that the EMS can reserve a configurable portion of battery state of charge for backup or another defined purpose.

Time-of-Use Optimization Supported

Indicates that the EMS can schedule or optimize energy use according to time-dependent electricity tariffs.

Dynamic Tariff Optimization Supported

Indicates that the EMS can optimize operation using changing electricity-price or tariff information.

Energy Price Signal Input Supported

Indicates that external electricity-price information can be received for use by energy-management logic.

Day-Ahead Energy Price Input Supported

Indicates that the EMS can receive day-ahead electricity-price data for scheduling or optimization.

PV Generation Forecast Supported

Indicates that expected photovoltaic generation can be forecast or imported for use by EMS optimization.

Load Forecast Supported

Indicates that future site electrical load can be forecast or imported for use by EMS optimization.

Weather Forecast Input Supported

Indicates that weather-forecast data can be used as an external input to energy-management or generation forecasting functions.

Maximum Forecast Horizonh

Maximum future time horizon supported by the EMS forecasting or forecast-assisted optimization function.

Scheduled Energy Dispatch Supported

Indicates that generation, storage or controllable loads can be dispatched according to a time-based energy schedule.

Minimum Energy Dispatch Intervals

Shortest manufacturer-supported time interval between scheduled energy-dispatch setpoints or control periods.

Controllable Asset Types

Types of electrical generation, storage or load assets that the EMS can actively coordinate or control.

External Energy Meter Integration Supported

Indicates that one or more external electricity meters can provide measurements to the EMS for control, optimization or monitoring.

Local Energy Optimization Supported

Indicates that energy-management optimization can execute locally on the product without requiring continuous cloud-side computation.

Cloud Energy Optimization Supported

Indicates that manufacturer-supported cloud services can perform or participate in energy-management optimization.

Offline Energy Management Supported

Indicates that core energy-management control remains available during loss of external Internet or cloud connectivity.

Control Command Acknowledgement Supported

Indicates that controlled assets can acknowledge receipt or acceptance of EMS control commands.

Control Setpoint Feedback Supported

Indicates that the EMS can read back the active or accepted control setpoint from a controlled asset.

Controlled Asset Availability Monitoring Supported

Indicates that the EMS can determine whether a configured controllable energy asset is currently available for control.

Controlled Asset Communication Status Monitoring Supported

Indicates that communication status of individual controlled energy assets can be monitored by the EMS.

Remote Energy Setpoint Control Supported

Indicates that energy, power, battery or site operating setpoints can be modified through a supported remote interface.

Control Source Priority Configurable

Indicates that priority between local, remote, cloud, schedule or external supervisory control sources can be configured.

Status LED Count

Number of integrated LEDs used to indicate product status or operating modes.

Event Log Supported

Indicates whether the product can store an internal event log.

Communication Supported

Indicates whether the product supports digital data exchange with external devices or systems.

Communication Protocols

List of supported digital data communication protocols.

Communication Interfaces

List of supported physical or logical digital communication interfaces.

Integrated Web Server

Indicates whether an integrated web server or web interface is provided for access to product functions.

Remote Configuration Supported

Indicates whether specified product settings can be read or changed remotely through a supported communication interface.

Remote Diagnostics Supported

Indicates whether diagnostic information, status data, or fault information can be obtained remotely.

Data Logger Supported

Indicates whether a data-logging function is provided for recording supported measurements, states, or process parameters.

Configurable Data Logger Trigger

Indicates whether the user can configure the condition that triggers or starts data logging.

Status Indicator Present

Indicates whether the product has a local visual or mechanical indicator of operating, fault, or end-of-life status.

Status Indicator Types

Types of local visual or mechanical status indication provided by the product design.

Firmware Updatable

Indicates that device firmware can be updated by a manufacturer-supported procedure.

Ethernet IP Address Assignment Methods

Supported methods for assigning network-layer addresses to the Ethernet interface.

IPv6 Supported

Indicates support for Internet Protocol version 6 communication.

Automatic Data Push Supported

Indicates that measured or logged data can be transmitted automatically without an explicit polling request.

Cloud Connectivity Supported

Indicates manufacturer-supported communication with a cloud or remote Internet service.

API Access Supported

Indicates that measurement, status or configuration data can be accessed through a documented application programming interface.

Supported API Types

Application programming interface types supported by the product or its integrated communication service.

Remote Firmware Update Supported

Indicates that firmware can be updated through a supported local or remote data communication interface.

Communication Watchdog Supported

Indicates that loss or inactivity of a communication link can be detected by an internal communication watchdog.

Configurable Communication Timeout

Indicates that the timeout used to detect communication loss or inactivity can be configured.

Minimum Communication Timeouts

Minimum configurable communication timeout.

Maximum Communication Timeouts

Maximum configurable communication timeout.

Communication Failure Alarm Supported

Indicates that loss of an expected communication connection can generate a local or remote alarm or diagnostic condition.

Communication Statistics Supported

Indicates that communication activity or communication health statistics can be read for diagnostic purposes.

Communication Error Counter Supported

Indicates that communication errors can be accumulated and read through the product diagnostics.

Communication Diagnostics Supported

Indicates that communication-interface faults, states or network conditions can be diagnosed by the product.

Standards and Compliance22
Conformity Regions

Regions or markets for which the manufacturer declares regulatory or certification compliance of the product.

Certification and Conformity Marks

Certification, market-approval, or conformity marks applicable to the product.

Primary Product Standard

Primary normative document or standard according to which the manufacturer classifies or assesses the product.

Additional Standards

Additional normative documents and standards declared by the manufacturer as applicable to the product.

Declaration of Conformity Available

Indicates whether an official declaration of conformity is available for the product.

Manufacturer Declaration Available

Indicates whether a separate manufacturer declaration concerning declared product characteristics or conformity is available.

Certificate Available

Indicates whether a certificate relating to the declared certification or conformity of the product is available.

Certificate Number

Identification number of the certificate relating to the product or its certified version.

Certification Body

Name of the organization that issued the certificate or performed the relevant conformity assessment.

Third-Party Tested

Indicates whether the product was tested by an organization independent of the manufacturer.

CE Marked

Indicates whether the CE marking is applied to the product where applicable.

UKCA Marked

Indicates whether the UKCA marking is applied to the product where applicable.

EAC Marked

Indicates whether the EAC marking is applied to the product where applicable.

UL Listed

Indicates whether the product has a declared UL Listed certification or recognition status.

UL Recognized

Indicates whether the product has a declared UL Recognized certification or recognition status.

cULus Marked

Indicates whether the cULus mark is applied to the product where applicable.

CSA Certified

Indicates whether the product has a declared CSA certification or recognition status.

TÜV Certified

Indicates whether the product has a declared TÜV certification or recognition status.

VDE Certified

Indicates whether the product has a declared VDE certification or recognition status.

RoHS Compliant

Indicates whether product compliance with applicable RoHS restrictions on hazardous substances has been declared.

REACH Compliant

Indicates whether the manufacturer declares compliance of the product with applicable REACH Regulation requirements.

WEEE Applicable

Indicates whether the product falls within the scope of WEEE requirements for waste electrical and electronic equipment.

Logistics11
Net Weightkg

Mass of the product itself, excluding transport packaging, additional accessories, and external equipment.

Gross Weightkg

Mass of the product together with its individual packaging and the accessories included in it.

Package Widthmm

External horizontal dimension of the product's individual package.

Package Heightmm

External vertical dimension of the product's individual package.

Package Depthmm

External depth dimension of the product's individual package.

Packaging Type

Design type of the product's individual or transport packaging.

Units per Package

Number of individual products contained in one packaging unit at the specified level.

Country of Origin

Country of origin of the goods declared for customs or commercial purposes.

Country of Manufacture

Country in which the product was manufactured or its principal manufacturing operation was performed.

HS Code

Commodity code under the international Harmonized Commodity Description and Coding System.

Combined Nomenclature Code

Commodity code under the Combined Nomenclature of the European Union.