TRASA3 Knowledge Base

Electrical Component Parameter Reference

An open technical reference for electrical component types, their applications, and selection parameters.

This material is also available in PL and RU.

Device description

Motor / Drive Cable

Power cable intended to connect an electric motor to a VFD, servo drive, spindle drive, or other electronic drive system.

A motor/drive cable carries power from the output of a VFD, servo drive, or other electronic converter to the motor. Unlike conventional mains supply, it commonly operates with PWM waveforms having very steep voltage edges.

The insulation must therefore withstand repetitive impulse stress, and the construction must address EMC effects associated with drive switching. The cable should retain suitable performance at the voltage and switching conditions of the drive.

Low and suitably balanced resistance of the motor conductors and effective screening are also important. The screen supports reduction of emissions generated by the inverter or servo drive.

The same sheath may contain additional conductors for a motor holding brake and other auxiliary circuits.

Selection criteria include rated voltage, motor current, power-core cross-section, screening, number of brake conductors, flexibility, and installation method. For moving applications, dynamic bend radius and repetitive-flex life are additional key characteristics.

Components in this subcategory

Motor and drive cables for VFDs, servo drives, spindle drives, and other PWM motor applications.

Available parameters

Motor / Drive Cable

38 parameters
General3
Product Series

Commercial or technical designation of a manufacturer's product family sharing a common design and compatible characteristics.

Application

Range of tasks and systems for which the manufacturer recommends the component.

Intended Use

Primary function of the device and its intended use as defined by its design and the manufacturer's documentation.

Dimensions5
Lengthmm

External linear dimension of the product along its longitudinal direction or principal length axis.

Diametermm

Transverse dimension of a product or its circular element measured through the centre between opposite points of the circumference.

Net Weightkg

Mass of the product itself, excluding transport packaging, additional accessories, and external equipment.

Minimum Bend Radiusmm

Minimum bend radius declared by the manufacturer at which installation or operation of the product is permitted without unacceptable damage.

Minimum Dynamic Bend Radiusmm

Minimum manufacturer-declared bend radius for repeated dynamic flexing under the specified operating conditions.

Materials and Finish8
Conductor Material

Primary electrically conductive material used for the cable conductors.

Conductor Class

Construction or flexibility class assigned to the conductor, including applicable IEC conductor classes.

Insulation Material

Primary electrical insulation material applied to or integrated with the conductive part of the product.

Outer Sheath Material

Primary material of the outer protective sheath or jacket of a cable.

Outer Sheath Color

Color of the distinct outer sheath or jacket.

Shielded

Indicates that the cable incorporates an electrical or electromagnetic shield.

Shield Material

Primary material and construction of the electrical cable shield.

Shield Coverage%

Manufacturer-declared geometrical coverage of a braided or equivalent cable shield.

Electrical Parameters11
Rated VoltageV

Voltage value assigned to the product by the manufacturer for specified application conditions and characteristics.

Conductor Count

Total number of individually insulated or functionally separate electrical conductors contained in the cable or cable assembly.

Power Conductor Count

Number of current-carrying power conductors, excluding PE and dedicated control or pilot conductors.

Nominal Conductor Cross-Sectionmm²

Manufacturer-declared nominal conductor cross-section assigned to the relevant connection system.

Protective Conductor Present

Indicates that the cable construction includes a dedicated protective-earth conductor.

Protective Conductor Cross-Sectionmm²

Nominal cross-section of the protective-earth conductor incorporated in the cable.

Wire Pair Count

Number of balanced wire pairs connected through, transmitted through, or protected by the product.

Cable Capacitance per Unit LengthµF/km

Manufacturer-declared cable capacitance per unit length under the stated electrical configuration and test conditions.

Cable Inductance per Unit LengthmH/km

Manufacturer-declared cable inductance per unit length under the stated electrical configuration and reference conditions.

PWM Drive Motor Cable Suitable

Indicates manufacturer-declared suitability for motor supply from PWM VFD/servo drives including applicable insulation and EMC stresses.

Brake Conductor Count

Number of dedicated conductors used to supply or control a motor holding brake within the cable.

Environmental Conditions9
Minimum Operating Temperature°C

Minimum ambient temperature at which normal operation of the product is permitted.

Maximum Operating Temperature°C

Maximum ambient temperature at which normal operation of the product is permitted.

Oil Resistant

Indicates whether the product materials retain their declared properties when exposed to the specified oils.

Coolant Resistant

Indicates whether the product materials retain their declared properties when exposed to the specified coolants.

Torsion Resistant

Indicates manufacturer-declared resistance to repeated or specified torsional mechanical loading.

Dynamic Flexing Supported

Indicates suitability of the product for repeated dynamic flexing during operation, rather than only for bending during installation.

Maximum Flex Cyclescycles

Maximum declared or qualified number of flexing cycles under the specified bend radius and test conditions.

Flame Retardant

Indicates the manufacturer-declared ability of a material or product to limit the spread of combustion under specified test conditions.

Halogen-Free

Indicates whether the product material is classified as halogen-free according to the characteristics declared by the manufacturer.

Standards and Compliance2
CE Marked

Indicates whether the CE marking is applied to the product where applicable.

RoHS Compliant

Indicates whether product compliance with applicable RoHS restrictions on hazardous substances has been declared.