Electrical Component Parameter Reference

An open technical reference for electrical component types, their applications, and selection parameters.

This material is also available in PL and RU.

Device description

Medium-Voltage Power Cable

Screened power cable intended for transmission of electrical energy in medium-voltage networks.

A medium-voltage power cable is intended for networks with rated voltages above the low-voltage range. It is used in distribution systems, feeders, and other power circuits requiring controlled electric-field distribution.

A typical construction includes a conductor screen, main insulation, insulation screen, and metallic screen. This arrangement limits electric-field concentration and provides defined operating conditions for the insulation system.

Depending on the design, additional layers may include a metallic sheath, longitudinal water-blocking elements, or a radial water barrier. Conductor construction and insulation material, such as XLPE or EPR, are also important.

Key electrical characteristics include U₀/U/Um, power-frequency test voltage, impulse withstand, partial-discharge level, and metallic-screen characteristics. Cable capacitance and inductance are also relevant to network design.

Selection criteria include system voltage, load current, short-circuit current, screen construction, grounding arrangement, installation conditions, and moisture-protection requirements.

For typical MV cable designs, declared compliance with IEC 60502-2 and other standards applicable to the specific construction and market is an important selection criterion.

Components in this subcategory

Screened medium-voltage power cables with XLPE, EPR, or other insulation systems for distribution networks.

Available parameters

Medium-Voltage Power Cable

170 parameters
General4
Product Series

Commercial or technical designation of a manufacturer's product family sharing a common design and compatible characteristics.

Application

Range of tasks and systems for which the manufacturer recommends the component.

Intended Use

Primary function of the device and its intended use as defined by its design and the manufacturer's documentation.

National Type Designation

National standardized or commonly recognized type designation assigned to the wire or cable, where applicable.

Dimensions20
Cable Cross-Section Shape

Overall external cross-sectional shape of the complete cable. This is distinct from conductor_shape, which describes the shape of an individual electrical conductor.

Widthmm

External horizontal dimension of the product between its outermost lateral points.

Lengthmm

External linear dimension of the product along its longitudinal direction or principal length axis.

Heightmm

External vertical dimension of the product from its lowest to its highest point.

Diametermm

Transverse dimension of a product or its circular element measured through the centre between opposite points of the circumference.

Net Weightkg

Mass of the product itself, excluding transport packaging, additional accessories, and external equipment.

Nominal Conductor Cross-Sectionmm²

Manufacturer-declared nominal conductor cross-section assigned to the relevant connection system.

Strand Diametermm

Nominal diameter of an individual metallic strand forming the conductor.

Conductor Diametermm

Overall nominal diameter of the conductive body before insulation or outer covering.

Insulation Thicknessmm

Nominal thickness of the electrical insulation layer of the product.

Outer Sheath Thicknessmm

Nominal thickness of the external protective cable sheath.

Power Conductor Cross-Sectionmm²

Nominal cross-section of each equivalent primary power conductor in the cable assembly.

Protective Conductor Cross-Sectionmm²

Nominal cross-section of the protective-earth conductor incorporated in the cable.

Mass per Meterkg/m

Manufacturer-declared product mass per unit length.

Neutral Conductor Cross-Sectionmm²

Nominal cross-section of the dedicated neutral conductor incorporated in the cable.

Inner Sheath Thicknessmm

Nominal thickness of the cable inner sheath or inner covering.

Armour Wire Diametermm

Nominal diameter of an individual armour wire where wire armour is used.

Armour Thicknessmm

Nominal thickness of the armour layer or armour element where applicable.

Metallic Sheath Thicknessmm

Nominal thickness of the continuous metallic cable sheath.

Metallic Screen Wire Diametermm

Nominal diameter of an individual wire forming the metallic cable screen.

Capacity and Layout10
Conductor Construction

Physical construction of the current-carrying conductor, such as solid, stranded, compacted, bunched or segmented.

Conductor Class

Construction or flexibility class assigned to the conductor, including applicable IEC conductor classes.

Strand Count

Number of individual metallic strands forming the electrical conductor.

Conductor Shape

Geometrical shape of the conductor cross-section.

Insulation Layer Count

Number of distinct electrical insulation layers in a multilayer or laminated construction.

Conductor Count

Total number of individually insulated or functionally separate electrical conductors contained in the cable or cable assembly.

Power Conductor Count

Number of current-carrying power conductors, excluding PE and dedicated control or pilot conductors.

Neutral Conductor Present

Indicates that the cable construction includes a dedicated neutral conductor.

Protective Conductor Present

Indicates that the cable construction includes a dedicated protective-earth conductor.

Metallic Screen Wire Count

Number of individual metallic screen wires used in a wire-screen construction.

Materials and Finish26
Color

Primary visually perceived colour of the product's external surface.

Conductor Material

Primary electrically conductive material used for the cable conductors.

Material Grade

Grade, alloy, class, or technical designation of the product's primary material.

Conductor Surface Finish

Metallic surface finish or plating applied to the electrical conductor.

Material Purity%

Manufacturer-declared material purity or principal-element content.

Coating Thicknessµm

Thickness of the coating layer applied to the surface of the product or one of its parts.

Insulated

Indicates whether functional or protective electrical insulation is provided over all or part of the conductive surface of the product.

Insulation Material

Primary electrical insulation material applied to or integrated with the conductive part of the product.

Insulation Color

Color of the primary electrical insulation layer surrounding the conductor.

Outer Sheath Present

Indicates that the insulated conductor has a distinct outer sheath or jacket in addition to its primary electrical insulation.

Outer Sheath Material

Primary material of the outer protective sheath or jacket of a cable.

Outer Sheath Color

Color of the distinct outer sheath or jacket.

Separator Present

Indicates that a separator, wrapping or release layer is provided between conductor, insulation or sheath layers.

Separator Material

Material of the separator, wrapping or release layer used in the wire construction.

Surface Marking Present

Indicates that identification, rating or certification information is printed, embossed or otherwise marked on the outer surface.

Surface Marking Text

Manufacturer-declared identification or rating marking printed or embossed on the outer surface of the product.

Surface Marking Method

Method used to apply identification or rating marking to the outer surface.

Inner Sheath Present

Indicates that the cable contains a distinct inner sheath or inner covering beneath the outer sheath or armour.

Inner Sheath Material

Primary material of the cable inner sheath or inner covering.

Filler Present

Indicates that filler material is used between cable cores to form or stabilize the cable construction.

Filler Material

Primary material used as filler between cable cores.

Armour Material

Primary metallic material used for the cable armour.

Longitudinal Water-Blocking Material

Primary material or technology used to provide longitudinal water blocking within the cable construction.

Metallic Sheath Present

Indicates that the cable incorporates a continuous metallic sheath distinct from the metallic screen.

Metallic Sheath Material

Primary metal used for the continuous metallic sheath of the cable.

Metallic Sheath Construction

Mechanical construction of the continuous metallic sheath.

Mounting and Installation6
Installation Location

Permissible installation location of the product: indoors, outdoors, in a technical area, or as part of equipment.

Flexible

Indicates the ability of the product to bend or change shape within its design limits without loss of normal function.

Minimum Bend Radiusmm

Minimum bend radius declared by the manufacturer at which installation or operation of the product is permitted without unacceptable damage.

Cable Installation Methods

Manufacturer-declared or standardized installation and routing methods for which the cable is suitable. This describes how the cable itself may be laid or routed and is distinct from mounting_type used for mounting standalone products.

Maximum Pulling ForceN

Maximum manufacturer-declared pulling or installation force that may be applied to the product without mechanical damage.

Suitable for Direct Burial

Indicates that the cable is manufacturer-declared as suitable for direct burial in soil without an additional continuous cable duct or conduit.

Electrical Parameters34
Electrical Conductivity%

Manufacturer-declared electrical conductivity of the material, expressed as percent IACS where this convention is applicable.

Intended Conductor Roles

Electrical conductor roles for which the wire is manufacturer-declared, standardized or specifically identified as suitable.

Nominal DC Conductor Resistance at 20 °COhm/km

Manufacturer-declared nominal DC resistance of the conductor at 20 °C, normalized to one kilometre of conductor length.

Maximum DC Conductor Resistance at 20 °COhm/km

Maximum manufacturer-declared DC resistance of the conductor at 20 °C, normalized to one kilometre of conductor length.

Current-Carrying CapacityA

Manufacturer-declared continuous current-carrying capacity under the stated reference installation and thermal conditions. Installation-dependent rating tables may require a future normalized structure.

Maximum Continuous Conductor Temperature°C

Maximum manufacturer-declared conductor temperature permitted during continuous normal operation.

Maximum Short-Circuit Conductor Temperature°C

Maximum manufacturer-declared conductor temperature permitted under short-circuit conditions.

1-Second Short-Circuit CurrentkA

Manufacturer-declared short-circuit current withstand capability for a one-second duration under the specified thermal conditions.

Temperature Coefficient of Resistance1/K

Manufacturer-declared temperature coefficient describing the change in conductor electrical resistance with temperature.

Rated Voltage U₀V

Rated voltage U₀ between an insulated conductor and earth or metallic covering, where the product uses U₀/U voltage designation.

Rated Voltage UV

Rated voltage U between conductors of a system, where the product uses U₀/U voltage designation.

Minimum Insulation Resistance ConstantMOhm*km

Minimum manufacturer-declared insulation resistance normalized as the resistance-length product, typically used for insulated wires and cables.

Dielectric StrengthkV/mm

Manufacturer-declared dielectric strength of the insulation material or insulation system expressed per unit thickness.

Maximum System Voltage UmV

Maximum system voltage Um associated with the cable rated-voltage designation U0/U (Um).

Conductor Screen Present

Indicates that a semiconductive conductor-screen layer is provided between the conductor and the primary insulation.

Conductor Screen Construction

Construction method of the semiconductive conductor-screen layer used for electric-field control.

Insulation Screen Present

Indicates that a semiconductive insulation-screen layer is provided over the primary insulation.

Insulation Screen Construction

Construction method of the semiconductive insulation-screen layer used for electric-field control.

Metallic Screen Present

Indicates that the cable incorporates a metallic screen outside the insulation screen.

Metallic Screen Type

Construction of the metallic cable screen, such as copper wires, metallic tape or a combined wire-and-tape screen.

Metallic Screen Cross-Sectionmm²

Nominal total conductive cross-section of the metallic cable screen.

Power-Frequency Test VoltagekV

Manufacturer-declared power-frequency AC test voltage applied during the applicable cable electrical test.

Lightning Impulse Withstand VoltagekV

Manufacturer-declared lightning-impulse withstand voltage of the cable insulation system under the applicable test method.

Partial Discharge Test VoltagekV

Voltage at which the declared partial-discharge magnitude is measured during the applicable cable test.

Maximum Partial DischargepC

Maximum manufacturer-declared apparent partial-discharge magnitude measured under the stated test voltage and conditions.

Semiconductive Oversheath Layer Present

Indicates that the non-metallic oversheath incorporates or is covered by a semiconductive layer intended for testing or bonding functions.

Oversheath Electrical Test VoltagekV

Manufacturer-declared voltage used for the applicable electrical integrity test of the non-metallic cable oversheath.

Metallic Screen 1-Second Short-Circuit CurrentkA

Manufacturer-declared one-second short-circuit current capability of the metallic cable screen or equivalent metallic screening system.

Insulation Screen Removal Type

Manufacturer-declared construction of the insulation screen with respect to removal during cable preparation, such as bonded or strippable.

Maximum Metallic Screen DC Resistance at 20 °COhm/km

Maximum manufacturer-declared DC resistance of the metallic screen at 20 °C, normalized per kilometre of cable length.

Cable Capacitance per Unit LengthµF/km

Manufacturer-declared cable capacitance per unit length under the stated electrical configuration and test conditions.

Cable Inductance per Unit LengthmH/km

Manufacturer-declared cable inductance per unit length under the stated electrical configuration and reference conditions.

Cable Charging Current per Unit LengthA/km

Manufacturer-declared capacitive charging current per unit cable length at the stated system voltage and frequency.

Dielectric Loss Factor

Manufacturer-declared dielectric loss factor, commonly expressed as tan delta, under the stated voltage, frequency and temperature conditions.

Protection and Safety18
Abrasion Resistant

Indicates that the cable outer construction is designed or qualified for enhanced abrasion resistance.

Crush Resistant

Indicates manufacturer-declared resistance to mechanical crushing or compressive loading under the applicable test conditions.

Halogen-Free

Indicates whether the product material is classified as halogen-free according to the characteristics declared by the manufacturer.

Flame Retardant

Indicates the manufacturer-declared ability of a material or product to limit the spread of combustion under specified test conditions.

Low Smoke

Indicates manufacturer-declared low-smoke performance of the cable materials.

Limiting Oxygen Index%

Manufacturer-declared limiting oxygen index of the applicable insulation, sheath or complete product material system.

Minimum Smoke Light Transmittance%

Minimum manufacturer-declared light transmittance measured during the applicable smoke-density test.

Maximum Halogen Acid Gas Content%

Maximum manufacturer-declared halogen acid gas content determined for the applicable cable material or product construction.

Minimum Combustion Gas pH

Minimum manufacturer-declared pH value of the aqueous solution obtained from gases evolved during combustion.

Maximum Combustion Gas ConductivityµS/mm

Maximum manufacturer-declared conductivity measured for the aqueous solution obtained from gases evolved during combustion.

Armoured

Indicates that the cable incorporates a mechanical armour layer.

Armour Type

Mechanical construction of the cable armour layer.

Fire Propagation Resistant

Indicates whether the material or construction limits flame propagation in the specified test.

Fire Resistance Class

Classification designation of the product's ability to maintain specified properties when exposed to fire for a defined period.

Longitudinal Water Blocking

Indicates that the cable construction includes barriers intended to limit longitudinal water propagation along the cable.

Longitudinal Water Penetration Test Compliant

Indicates manufacturer-declared compliance with the applicable longitudinal water-penetration test for the cable construction.

Radial Water Barrier Present

Indicates that the cable incorporates a continuous construction layer intended to limit radial water ingress through the cable covering.

Radial Water Barrier Type

Construction type of the radial moisture or water barrier incorporated in the cable.

Environmental Conditions15
Installation Environment

Environmental conditions under which installation and operation of the product are permitted.

Water Resistant

Indicates manufacturer-declared resistance to water exposure under the applicable product or test conditions.

Weather Resistant

Indicates whether the product is designed for the combination of weather influences specified by the manufacturer.

Minimum Operating Temperature°C

Minimum ambient temperature at which normal operation of the product is permitted.

Maximum Operating Temperature°C

Maximum ambient temperature at which normal operation of the product is permitted.

Minimum Storage Temperature°C

Minimum ambient temperature permitted during storage of the product while not in operation.

Maximum Storage Temperature°C

Maximum ambient temperature permitted during storage of the product while not in operation.

Minimum Installation Temperature°C

Minimum ambient temperature at which the manufacturer permits installation of the product.

Maximum Installation Temperature°C

Maximum ambient temperature at which the manufacturer permits installation of the product.

Maximum Relative Humidity%

Maximum relative air humidity permitted for the declared operating or test condition.

UV Resistant

Indicates whether the material and coating are designed to withstand ultraviolet radiation.

Oil Resistant

Indicates whether the product materials retain their declared properties when exposed to the specified oils.

Chemical Resistance

Groups of chemicals or environments whose effects the product can withstand under the declared conditions.

Fuel Resistant

Indicates whether the product materials retain their declared properties when exposed to the specified fuels.

Ozone Resistant

Indicates whether the product materials retain their declared properties when exposed to ozone.

Special Features2
Tensile StrengthMPa

Manufacturer-declared tensile strength of the material for the specified material condition, grade, or temper.

Elongation at Break%

Manufacturer-declared elongation at break or after fracture under the specified tensile-test conditions.

Standards and Compliance21
IEC / EN 60228 Compliant

Manufacturer-declared compliance of the conductor construction, nominal cross-section and resistance characteristics with IEC 60228 or its applicable EN adoption.

Certification and Conformity Marks

Certification, market-approval, or conformity marks applicable to the product.

CE Marked

Indicates whether the CE marking is applied to the product where applicable.

RoHS Compliant

Indicates whether product compliance with applicable RoHS restrictions on hazardous substances has been declared.

REACH Compliant

Indicates whether the manufacturer declares compliance of the product with applicable REACH Regulation requirements.

IEC 60332-1-2 Compliant

Compliance with IEC 60332-1-2 vertical flame propagation test requirements applicable to a single insulated wire or cable.

IEC 60754-1 Compliant

Compliance with applicable IEC 60754-1 requirements for determination of halogen acid gas content from cable materials.

IEC 60754-2 Compliant

Compliance with applicable IEC 60754-2 requirements for determination of acidity and conductivity of gases evolved during combustion.

IEC 61034-2 Compliant

Compliance with applicable IEC 61034-2 smoke-density test requirements for burning cables or wires.

CPR Reaction-to-Fire Class

Manufacturer-declared reaction-to-fire class for electric cables or wires under the applicable CPR classification system.

CPR Smoke Production Class

Manufacturer-declared supplementary CPR smoke-production classification.

CPR Flaming Droplets Class

Manufacturer-declared supplementary CPR classification for flaming droplets or particles.

CPR Acidity Class

Manufacturer-declared supplementary CPR acidity classification based on combustion-gas pH and conductivity.

CPR Flame Spread Heightmm

Manufacturer-declared or test-reported vertical flame spread height used in the applicable reaction-to-fire assessment.

CPR Total Heat Release at 1200 sMJ

Test-reported total heat release over 1200 seconds where declared for CPR reaction-to-fire classification.

CPR Peak Heat Release RatekW

Test-reported peak heat release rate where declared for CPR reaction-to-fire classification.

CPR FIGRAW/s

Fire growth rate index reported for the applicable CPR reaction-to-fire test.

CPR Total Smoke Production at 1200 sm²

Test-reported total smoke production over 1200 seconds where declared for CPR classification.

CPR Peak Smoke Production Ratem²/s

Test-reported peak smoke production rate where declared for CPR classification.

EN 50575 Compliant

Manufacturer-declared compliance with EN 50575 where the wire or cable is placed on the market for permanent incorporation in construction works and the standard is applicable.

IEC 60502-2 Compliant

Manufacturer-declared compliance with IEC 60502-2 for applicable power cables with extruded insulation for rated voltages from 6 kV up to 30 kV.

Logistics14
Gross Weightkg

Mass of the product together with its individual packaging and the accessories included in it.

Package Widthmm

External horizontal dimension of the product's individual package.

Package Heightmm

External vertical dimension of the product's individual package.

Package Depthmm

External depth dimension of the product's individual package.

Package Volumem³

Calculated or declared external volume of the product's individual package.

Packaging Type

Design type of the product's individual or transport packaging.

Packaging Material

Primary materials from which the product packaging is made.

Package Tare Weightkg

Mass of the empty packaging without the product and its accessories.

Units per Package

Number of individual products contained in one packaging unit at the specified level.

Recyclable Packaging

Indicates whether the packaging used is declared recyclable as secondary raw material.

Reusable Packaging

Indicates whether the packaging is designed for reuse without changing its primary purpose.

Returnable Packaging

Indicates whether the packaging is intended to be returned to the supplier, manufacturer, or another participant in the logistics chain.

Country of Origin

Country of origin of the goods declared for customs or commercial purposes.

HS Code

Commodity code under the international Harmonized Commodity Description and Coding System.