TRASA3 Knowledge Base

Electrical Component Parameter Reference

An open technical reference for electrical component types, their applications, and selection parameters.

This material is also available in PL and RU.

Device description

SPD Replacement Cartridge

Replaceable protective cartridge for a modular surge protective device, containing the main surge-limiting element.

An SPD replacement cartridge contains the primary protective element and is installed in the fixed base of a modular surge protective device.

When its protection life is exhausted or the cartridge fails, it can be replaced without removing the complete base or reconnecting field conductors.

The electrical characteristics of the replacement module must match the type and series of the SPD base.

Selection criteria include SPD type, rated and maximum continuous operating voltage Uc, protection level Up, discharge-current ratings and compatibility with the specific base.

Components in this subcategory

Replacement cartridges for modular surge protective devices.

Available parameters

SPD Replacement Cartridge

46 parameters
General3
Product Series

Commercial or technical designation of a manufacturer's product family sharing a common design and compatible characteristics.

Application

Range of tasks and systems for which the manufacturer recommends the component.

Intended Use

Primary function of the device and its intended use as defined by its design and the manufacturer's documentation.

Dimensions4
Widthmm

External horizontal dimension of the product between its outermost lateral points.

Heightmm

External vertical dimension of the product from its lowest to its highest point.

Depthmm

External distance between the foremost and rearmost surfaces of the product.

Net Weightkg

Mass of the product itself, excluding transport packaging, additional accessories, and external equipment.

Materials and Finish3
Material

Primary material from which the product is manufactured.

Color

Primary visually perceived colour of the product's external surface.

Surface Finish

Type of final surface finish of the product determining its appearance and service properties.

Mounting and Installation4
Mounting Type

Installation arrangement permitted by the product design, such as wall-mounted, flush-mounted, floor-mounted, or another specified mounting type.

Mounting Method

Method used to mechanically secure the product to a support, surface, or load-bearing structure.

Orientation

Permissible spatial orientation of the component during installation and operation.

Mounting Position on Device

Position of the accessory relative to the host switching or protective device, independent of the general installation orientation.

Electrical Parameters18
SPD Type

Declared type or combined type of surge protective device according to the applicable SPD product standard.

SPD Voltage Response Type

Functional response of the SPD to an overvoltage: voltage limiting, voltage switching, or a combination of both.

SPD Technology

Principal technologies or nonlinear protective components used by the product to limit or divert a surge overvoltage.

SPD Port Configuration

Constructional classification of an SPD by number of ports, for example one-port or two-port design according to the applicable standard.

Voltage Protection LevelV

Declared voltage protection level Up characterizing the limited voltage across the SPD during the specified standardized test.

Nominal Discharge CurrentkA

Nominal discharge current In declared for the SPD for the specified standardized current impulse waveform.

Maximum Discharge CurrentkA

Maximum discharge current Imax that the SPD is capable of withstanding for the specified standardized impulse waveform.

Impulse Discharge CurrentkA

Impulse discharge current Iimp used to characterize the ability of the SPD to withstand a high-energy current impulse.

Total Discharge CurrentkA

Declared total discharge current of a multipole or multimode SPD where the manufacturer specifies an overall value for the product.

Maximum Operating VoltageV

Maximum voltage at which continuous operation of the product is permitted under the conditions declared by the manufacturer.

Rated VoltageV

Voltage value assigned to the product by the manufacturer for specified application conditions and characteristics.

Rated CurrentA

Current assigned to the product by the manufacturer for the declared operating and thermal conditions.

Rated Insulation VoltageV

Voltage with reference to which the product's insulation clearances and dielectric properties are specified.

Rated Impulse Withstand VoltagekV

Peak value of an impulse voltage of specified waveform that the product insulation must withstand without breakdown.

Short-Circuit Current RatingkA

Manufacturer-declared permissible short-circuit current value for the product or assembly under specified conditions.

Response Timens

Manufacturer-declared response time of the relevant protective function of the product to a surge impulse.

SPD Failure Mode

Declared behaviour of the SPD at end of life or after failure of a protective element, including open-circuit or short-circuit state where provided by design.

SPD Connection Configuration

Declared connection topology of the SPD protective circuits defining their electrical connection to conductors of the protected system.

Protection and Safety1
IP Rating

Degree of enclosure protection against access to hazardous parts and ingress of solid objects and water, designated by the IP code.

Environmental Conditions4
Minimum Operating Temperature°C

Minimum ambient temperature at which normal operation of the product is permitted.

Maximum Operating Temperature°C

Maximum ambient temperature at which normal operation of the product is permitted.

Minimum Storage Temperature°C

Minimum ambient temperature permitted during storage of the product while not in operation.

Maximum Storage Temperature°C

Maximum ambient temperature permitted during storage of the product while not in operation.

Special Features3
Thermal Disconnector Present

Indicates whether a thermal disconnector is provided to disconnect the protective element in the event of overheating, degradation, or the specified fault condition.

Status Indicator Present

Indicates whether the product has a local visual or mechanical indicator of operating, fault, or end-of-life status.

Replaceable Protection Module

Indicates whether the protective module or SPD cartridge can be replaced without replacing the complete base part of the product.

Standards and Compliance6
CE Marked

Indicates whether the CE marking is applied to the product where applicable.

IEC 61643-01 Compliant

Indicates declared compliance with the applicable general requirements and test methods of IEC 61643-01 for low-voltage surge protective devices.

RoHS Compliant

Indicates whether product compliance with applicable RoHS restrictions on hazardous substances has been declared.

IEC 61643-11 Compliant

Indicates declared compliance with the applicable IEC 61643-11 requirements and test methods for SPDs connected to low-voltage AC systems.

REACH Compliant

Indicates whether the manufacturer declares compliance of the product with applicable REACH Regulation requirements.

UL 1449 SPD Type

SPD construction and installation type according to UL 1449 classification, distinct from IEC Type 1, Type 2, and Type 3 classification.